beautypg.com

Alpha Technologies CE3G User Manual

Page 14

background image

14

745-738-C0-001 Rev. A

1.2 Installation, continued

1.2.3 Gas Box Modifi cation

1. To make room for drilling, loosen fl are fi tting and rotate LFPS to the right.

Pivot assembly

Loosen fi tting

2. Pull the black and white LFPS wires through to the gas utility box enclosure. Take

care not to damage the connector contacts.

3. Loosen the existing bulkhead fi tting and remove.

4. Use #4 UNIBIT to enlarge and deburr the LFPS wire hole to 7/8".

Fig. 1-6, LFPS Assembly

Fig. 1-7, LFPS Wiring, Bulkhead Fitting

Fig. 1-8, Outside Bottom View, Gas Utility Box

3/4"

3.00"

+

Existing opening

for braided hose

7/8" dia. opening

for Strain Relief

Connector

5. Drill and deburr 7/8" dia. opening in bottom of gas box as indicated in Fig. 1-8.

6. Clean metal shavings from gas box and install strain relief connector.

Enlarge to 7/8" dia.