7 specifications, 1 dc input, 2 ac input (with transfer switch) – Alpha Technologies INVERTER 2000 User Manual
Page 22: 3 ac output, Pecifications, Dc input, Ac input (with transfer switch), Ac output, 7specifications

Alpha Technologies Ltd.
014-129-B2 Rev C WC
© 2010 Alpha
Technologies Ltd. ALPHA is a registered trademark of Alpha Technologies Ltd. All Rights Reserved.
Page 16 of 19
7
Specifications
7.1 DC Input
Nominal Voltage:
48Vdc
Operating Range:
40 to 60Vdc within rated limits
Under Voltage Warning Threshold: 45Vdc
Under Voltage Threshold:
40Vdc
Over Voltage Warning Threshold:
58Vdc
Over Voltage Threshold:
60Vdc
Inrush current:
<2 x I rated
Isolation DC-enclosure:
707Vdc (varistors and filter capacitor removed)/1min
Input Protection:
Reverse polarity protection
Psophometric Noise Voltage:
≤
1.0mV ITU-T O.41 (16.66 to 6000Hz)
Wide Band Noise:
<1.0mV (psophometric, 25Hz to 5kHz)
<20mVrms (25Hz to 20kHz)
Peak to Peak Noise:
<150mV up to 100MHz
7.2 AC Input (with transfer switch)
Voltage Range:
110/115/120Vac: 89 to 138Vac
208/220/230/240Vac: 176 to 276Vac
Over Voltage Threshold:
276 / 138Vac
Under Voltage Threshold:
176 / 89Vac
Frequency Range:
50/60 ±2.5% Hz
Back-feed Protection:
Comply with safety requirement
Transfer Time:
8ms when Inverter → Mains AC
10ms when Mains AC → Inverter
7.3 AC Output
Power Capacity:
2000VA/2000W
Waveform:
Pure sine wave
Power Factor:
1.0
Nominal Output Voltage:
110/115/120Vac or 208/220/230/240Vac
Voltage Regulation:
±2%
Output Frequency:
50/60Hz
Frequency Variation:
±0.5%
Frequency Setting:
Manually, field-selectable
Crest Factor:
3:1
T.H.D. (Current):
<3% for linear load, <5% for non-linear load
Capacitive/Inductive Load:
-1.0 to +1.0 without exceeding permissible distortion for resistive load
Efficiency:
>91%
Current Limitation:
Electronic current limitation at overloads and short circuits
Isolation AC-enclosure:
Basic isolation (Pri-Gnd) 2121Vdc/1min
Isolation AC-DC:
Reinforced isolation (Pri-Sec) 4242Vdc/1min
Surge Protection:
EN61000-4-5, Telcordia GR-1089 CORE, ANSI/IEEE C62.41, STD 587-
1980
Dynamic Response:
Better than ±10% according to IEC 62040-3 Class 1