3 unpacking and inspection – Alpha Technologies CFR 1500, CFR 1500RM User Manual
Page 10
4
1.3
Unpacking and Inspection
Carefully remove the UPS from its shipping container. Inspect the contents.
If items appear to be damaged or missing, contact Alpha Technologies and the
shipping company immediately. Most shipping companies have only a short claim
period. Make sure the following items have been included:
1. CFR Series UPS with AC line cord
2. Operator's Manual
3. Any other ordered options
SAVE THE ORIGINAL SHIPPING CONTAINER. In the event the UPS needs to be
returned for service, it should be packaged in its original shipping container. If the
original container is not available, make sure that the unit is packed with at least
three inches of shock-absorbing material to prevent shipping damage. NOTE: Do
not use popcorn-type material. Alpha Technologies is not responsible for damage
caused by the improper packaging of returned units.
PLEASE READ THE OPERATOR'S MANUAL.
Become familiar with the UPS front and rear panels. Review the drawings and
illustrations before proceeding with the UPS installation. If you have questions
regarding the safe installation or operation of the UPS, contact Alpha Technologies.
1. INTRODUCTION
Model #
Serial #
Options
Purchase date
Dealer name
City
State/Province
Zip/Postal Code
Country
Telephone #
COMPLETE THE FOLLOWING FOR YOUR RECORDS:
THIS UNIT WAS PURCHASED FROM:
69
NOTICE
This equipment generates, uses, and can radiate radio frequency energy if not
installed and used in accordance with the instructions contained in the manual.
It has been tested and found to comply with the limits established for a Class A
computing device pursuant to Part 15 of FCC rules and the radio interference
regulations of DOC which are designed to provide reasonable protection against
such interference when this type of equipment is operated in a commercial
environment. If the UPS appears to cause interference to radio or television
reception, which can be determined by switching the unit OFF and ON, relocate
the equipment and/or use an electrical circuit other than that used by the UPS.
6.6
Troubleshooting Guide
,
continued
6. MAINTENANCE
* ITEMS TO BE PERFORMED ONLY BY A QUALIFIED TECHNICIAN
SYMPTOM
CAUSE
REMEDY
No output voltage
during utility outage:
"LINE PRESENT" OFF
"LINE FAILURE" OFF
"LOW BATTERY
SHUTDOWN" ON
Batteries do not
charge:
"LOW BATTERY
SHUTDOWN"
ON
Battery voltage below
low voltage cutout
(after long outage).
or
Battery voltage below
low voltage cutout
(after several short
outages).
BATTERY breaker
tripped.
or
Loose battery cable
or connection.
or
Faulty batteries.
or
Open charger fuse.
Wait for line power to
return and recharge
batteries.
Wait for batteries to
recharge.
*Check batteries and
replace if necessary.
Reset breaker.
*Clean and tighten
connections.
*Check batteries and
replace if necessary.
*Check internal fuse on
main circuit board and
replace if necessary.