beautypg.com

E-rp-2m_2, Cla-val, Flow curves – Cla-Val RP2M User Manual

Page 2: Dimensions, Specifications, Material, Size a b

background image

We recommend providing adequate space around assembly for maintenance work and testing.

HEADLOSS-PSI

20

15

10

5

0

20

40

60

80

FLOW-GPM

50
RF

50

Flow Curves

1" Model RP-2

Dimensions

(In Inches)

�”x°����c���

gl

gf

m

f

hf

mf

of

gff
N��

����c���

kf

gff

�”x°����c���

hf

gl

gf

l

f

hf

kf

lf

mf

lf
��

����c���

if

3/4" Model RP-2

1-1/2" Model RP-2

Flow curves generated by the Foundation for Cross-Connection Control and Hydraulic Research University of Southern California.
*”Metered Rated Flow" Values adopted by the American Water Works Association and the New England Water Works Association

Specifications

Fluid: Potable Water/ Seawater

Hydrostatic Test Pressure:
to 300 psi

Military:

Shock qualified to MIL-S-901C

Vibration Qualified to MIL-STD-167B

Material:

Main Body Valve and Cover:

Bronze ASTM B-61

Main valve trim:

Monel & Delrin

Seals:

Buna-N

Diaphragm:

Nylon Reinforced Buna-N

Size: 3/4"

, 1", 1 1/4", 1 1/2"

End Detail:
Threaded: ANSI B 16.15

Maximum Working Pressure:
150 psi

Max. Temperature:
to 110°F

SIZE

A

B

(Max.)

C

(Max.)

WT.LBS

3/4"

11.60

3.65

6.00

15

1"

11.44

3.65

6.00

15

1-1/2"

14.81

4.00

6.19

25

Meter Rated Flow*

PO Box 1325 Newport Beach CA 92659-0325

Phone: 949-722-4800

Fax: 949-548-5441

CLA-VAL

CLA-VAL CANADA

CLA-VAL EUROPE

4687 Christie Drive
Beamsville, Ontario
Canada L0R 1B4
Phone: 905-563-4963
Fax: 905-563-4040

Chemin dés Mesanges 1
CH-1032 Romanel/
Lausanne, Switzerland
Phone: 41-21-643-15-55
Fax: 41-21-643-15-50

©

COPYRIGHT CLA-VAL 2013 Printed in USA

Specifications subject to change without notice.

www.cla-val.com

E-RP-2M (R-1/2013)

Represented By:

The reduced pressure principle backflow preventer shall
consist of two independently acting spring-loaded check
valves and an automatically operating pressure differential
relief valve, and shall have provision for installing properly
located test cocks. Operation shall be completed
automatic. All internal parts of the spring-loaded check
valves and the pressure differential relief valve must be
removable or replaceable without removal of the backflow
preventer form the line. the total head loss at rated flow
rate through the complete backflow preventer assembly

shall not exceed (select values as shown in the table). The
reduced pressure principle backflow preventer shall be the
Model RP-2M Shipboard Backflow Preventer as
manufactured by Cla-Val, Newport Beach, California.

Valve Size

Rated

Pressure Drop

in Inches

Flow

in PSI

3/4”

30

12.8

1”

50

12.25

1 1/2”

100

13.5