Cla-Val 50-49 User Manual
Page 11

Model 100-20 Flow Chart
(Based on normal flow through a wide open valve)
20 24
10
20
30 40
60 80 100
200
500
1000
2000
5000
10,000 20,000 50,000
1
2
3
4
6
8
10
20
30
40
60
80
100
5
3
Angle Valve Sizes (Inches)
Globe Valve Sizes (Inches)
3
4
6
8
10
12
6
8
16
Pressure Drop — psi
4
18
30
14
Flow Rate gpm (water)
K =
894d
4
C
2
v
L =
K
12 f
K Factor (Resistance Coefficient)
The Value of K is calculated from the formula:
(U.S. system units)
Equivalent Length of Pipe
Equivalent lengths of pipe (L) are determined from the formula:
(U.S. system units)
Fluid Velocity
Fluid velocity can be calculated from the following formula:
(U.S. system units)
d
V =
.4085 Q
2
d
C
V
Factor
Formulas for computing C Factor, Flow (Q) and Pressure Drop
V
( P):
C
V
=
Q
P
C
V
=
Q
P
C
V
=
Q
P
2
V
Where:
U.S. (gpm) @ 1 psi differential at 60 F water
(l/s) @ 1 bar (14.5 PSIG) differential
or
at 15 C water
inside pipe diameter of Schedule 40 Steel Pipe (inches)
friction factor for clean, new Schedule 40 pipe
(dimensionless) (from Cameron Hydraulic Data,
18th Edition, P 3-119)
Resistance Coefficient (calculated)
Equivalent Length of Pipe (feet)
Flow Rate in U.S. (gpm) or (l/s)
Fluid Velocity (feet per second) or (meters per second)
Pressure Drop in (psi) or (bar)
=
=
=
=
=
=
=
=
=
P
V
Q
L
K
f
d
C
Functional Data
Model 100-20
*Estimated
Valve Size
Inches
3
4
6
8
10
12
14
16
18
20
24
30
mm.
80
100
150
200
250
300
350
400
460
500
600
760
C V
Factor
Globe
Pattern
Gal./Min. (gpm.)
62
136
229
480
930
1458
1725
2110
2940*
3400*
4020
7900*
Litres/Sec. (l/s.)
15
32.5
55
115
223
350
414
506
705
816
965
1895
Angle
Pattern
Gal./Min. (gpm.)
—
135
233
545
—
—
—
—
—
—
—
—
Litres/Sec. (l/s.)
—
32
56
132
—
—
—
—
—
—
—
—
Equivalent
Length
of
Pipe
Globe
Pattern
Feet (ft.)
293
251
777
748
621
654
750
977
983
1125
3005
2130
Meters (m.)
89.3
76.4
237.1
228.1
189.5
199.4
228.7
298.1
299.9
343.2
916.6
649.6
Angle
Pattern
Feet (ft.)
—
254
751
580
—
—
—
—
—
—
—
—
Meters (m.)
—
77.6
229
176.9
—
—
—
—
—
—
—
—
K
Factor
Globe Pattern
20.6
12.7
23.1
15.7
10.4
8.5
8.9
10.2
8.4
8.8
19.1
10.5
Angle Pattern
—
12.9
22.3
12.2
—
—
—
—
—
—
—
—
Liquid Displaced
from Cover Chamber
When Valve Opens
Fl. Oz
—
—
—
—
—
—
—
—
—
—
—
—
U.S. Gal.
0.32
.08
.17
.53
1.26
2.51
4.0
4.0
9.6
9.6
9.6
29.0
ml
—
—
—
—
—
—
—
—
—
—
—
—
Litres
.12
.30
.64
2.0
4.8
9.5
15.1
15.1
36.2
36.2
36.2
110