beautypg.com

Deluge valve, Typical application, Specifications – Cla-Val 414-01 User Manual

Page 4: When ordering, please specify friction loss, Model

background image

100G

2100G

• U.L. Listed / U.L.C. Listed

• Globe or Angle Pattern

• Proven Reliable Design

The Cla-Val Model 100G/2100G Deluge Valve is designed for use in controlling

water flow to Deluge, Pre-Action, or Foam-Water type fire protection sprinkler

systems. This valve is U.L. Listed in "Special Systems Water Control Valves

Class I (VLFT)".

The Model 100G-2100G is a hydraulically-operated, diaphragm-actuated, globe

or angle pattern Deluge Valve. It consists of three major components: the body,

the cover, and the diaphragm assembly. The only moving part is the diaphragm

assembly. Packless construction and simplicity of design assures long service

life and dependable low maintenance for this valve. All ferrous parts are fusion

epoxy coated internally and externally for added corrosion resistance, along

with a delrin sleeve stem and teflon coated removable seat.

Typical Application

Deluge Valve

The Model 100G/2100G is installed to control the water flow to the

sprinklers in Deluge, Pre-Action, or Foam-Water type systems. A

simplified system is used to illustrate typical operation.

The Model 100G/2100G Deluge Valve (3) is

maintained in the closed position by means of

system water pressure controlled by a pilot

control (4). When the pilot control valve

receives a signal from the fire detection sys-

tem, it allows the deluge valve to open.

Firefighting water (1) then enters system

piping (5) and discharges from

sprinklers (6).

4

1

2

3

5

UL

®

Globe: 3" – 10"

Angle: 3" – 10"

Ductile Iron 150 ANSI B16.42 flanged

Cast Steel 150 ANSI B16.5 flanged

150 class, 250 psi maximum (Ductile Iron)

150 class, 285 psi maximum (Cast Steel)

300 class, 400 psi maximum

Water, to 180°F MAX.

Main Valve Body & Cover:

Ductile Iron ASTM A-536* UL, ULC

Cast Steel ASTM A216-WCB* UL, ULC

Nickel Aluminum Bronze ASTM B148 UL, ULC

Naval Bronze ASTM B61 UL, ULC

Super Duplex Stainless steel UNS32750 UL, ULC

Stainless Steel ASTM A743-CF-8M UL, ULC

Main Valve Internal Trim:

Bronze ASTM B61

Stainless Steel Type 303

Monel QQ-N-281 Class B

Diaphragm and Disc:

Buna-N

®

synthetic rubber

*Internally & Externally Epoxy Coated Standard

Sizes

End Details

Pressure Rating

Temperature Range

Materials

Specifications

1. Catalog No. 100G or 2100G

2. Size

3. Body and Cover Material

4. Globe or Angle Pattern

5. Pressure Class

6. Internal Trim Material

When Ordering, Please Specify

Friction Loss

For use in hydraulically calculated

systems, friction loss equivalent to:

100G (Globe):

3" Size=42 Ft. of 3" Pipe

4" Size=92 Ft. of 4" Pipe

6" Size=116 Ft. of 6" Pipe

8" Size=123 Ft. of 8" Pipe

10" Size=201 Ft. of 10" Pipe

2100G (Angle):

3" Size=33 Ft. of 3" Pipe

4" Size=44 Ft. of 4" Pipe

6" Size=79 Ft. of 6" Pipe

8" Size=105 Ft. of 8" Pipe

10" Size=153 Ft. of 10" Pipe

(1) From System Water Supply
(2) System Shut-off Valve (Visual Stem)
(3) Cla-Val Model 100G or 2100G
(4) Pilot Control System
(5) Sprinkler System Piping
(6) Sprinklers

MODEL