Cla-val – Cla-Val CDHS-33 User Manual

Page 2

background image

When Ordering, Please Specify

1. Catalog No. CDHS-33 (Orifice Downstream)

CDHS-33A (Orifice Upstream)

2. Materials

Pilot Control

Adjustment Range

70 to 480 inches H2O Differential

End Connection

3/8" NPT

Temperature Range

Water: to 180°F

Materials

Pilot Control: Bronze ASTM B62
Trim:Stainless Steel Type 303
Rubber:Buna-N

®

Synthetic Rubber

Available with optional Stainless Steel or Monel
materials at additional cost. Consult factory for details

Note: Available with Remote Sensing for orifice upstream,

specify CDHS-33A

Note: Total Shipping Weight: 8 Lbs.

Pilot Control Subassembly Specifications

CDHS-33 Electronic Actuator Specifications

PO Box 1325 Newport Beach CA 92659-0325

Phone: 949-722-4800

Fax: 949-548-5441

CLA-VAL

CLA-VAL CANADA

CLA-VAL EUROPE

4687 Christie Drive
Beamsville, Ontario
Canada L0R 1B4
Phone: 905-563-4963
Fax: 905-563-4040

Chemin dés Mesanges 1
CH-1032 Romanel/
Lausanne, Switzerland
Phone: 41-21-643-15-55
Fax: 41-21-643-15-50

©

COPYRIGHT CLA-VAL 2012 Printed in USA

Specifications subject to change without notice.

www.cla-val.com

E-CDHS-33 (R-7/2012)

Represented By:

CDHS-33 Purchase Specifications

The Electronic Actuated Rate of Flow Control Pilot shall have an integral hydraulic pilot and electronic controller contained in a IP-68 rated
submersible enclosure to provide interface between remote telemetry and valve set-point control. It will compare a remote analog command
signal with an internal position sensor signal and adjust the hydraulic pilot control spring mechanism to a new set-point position. Remote
analog signal input shall be isolated and reverse polarity protected. 4-20 mA actuator position feedback output shall be supplied standard. A
second command control input shall be from dry-contact switch closure for clockwise or counter clockwise actuator rotation.
If power fails, the control pilot valve shall continue to control main valve to last set-point command. If the Remote Set-Point signal
is lost the actuator is programmable to go to either the 4mA, Last, or 20mA command set-point. No mechanical adjustments shall
be necessary to the actuator. The low and high position range adjustment shall be accomplished only with valve manufacturer's
components and instructions to be supplied in a separate kit. The assembly shall be supplied with 30 feet of cable.

The Electronic Actuated Rate of Flow Pilot Control shall be Cla-Val Model CDHS-33 as manufactured by Cla-Val, Newport Beach, CA.

USB connection cable required when changing range

parameters or restoring range parameters after servicing

pilot control subassembly.

Options:

Re-ranging software - free download from www.cla-val.com.
Ranging software makes it easy to set low (4mA) and
high (20mA) set-point limits.

Supply Power Input:

12V to 24V DC
No Load draw: 50 mA
Max. Load draw: 250 mA

Remote Command Inputs:

4-20mA, analog signal

(isolated and reverse-polarity

protected)

Dry contact closure (CW/CCW)

Position Feedback Signal: 4-20 mA

Alarm Output:

Dry-contact closure (High/Low)

Speed of Rotation:

Adjustable On/Off time, max 6 rpm

Diagnostic:

LED Indicator

Loss of Power:

Actuator will remain in last commanded
position.

Loss of Signal Position:

Programmable - 4 mA, Last, or 20 mA

Electrical Connections:

Single, 30 feet of permanently attached
cable with color-coded power supply and
signal wires

Mechanical Specifications:

Environmental

Protection Class:

IP-68 (Temporary submersible)

Ambient Temperature: 15° to 150° F (-10° to 65° C)

Materials

Electronics Enclosure:

Anodized Aluminum

Mechanical Housing:

Bronze

Coupling Assembly:

Stainless Steel

Gear Train:

Stainless Steel, permanently lubricated