beautypg.com

Cla-val, Cdhs18, Cdc-1 – Cla-Val 49-01/649-01 Quick Manual User Manual

Page 2: Hytrol main valve

background image

CLA-VAL

Copyright Cla-Val 2008 Printed in USA Specifications subject to change without notice.

P.O. Box 1325

• Newport Beach, CA 92659-0325 • Phone: 949-722-4800 • Fax: 949-548-5441 • E-mail: [email protected] • Website cla-val.com

©

N-49-01 (R-9/08)

SERVICE SUGGESTIONS

SYMPTOM

Main valve
won't open.

Main valve
won't close.

PROBABLE CAUSE

Controls not adjusted properly.

Orifice port and/or orifice
sensing line clogged.

Control line shutoff cock to
cover, main valve outlet,
and/or orifice sensing line
closed.

Either of the pilot valves stuck
closed. Mineral deposits or
foreign matter under disc
retainer assembly.

Main valve stuck closed.
Mineral buildup on stem. Stem
damaged.

Controls not adjusted properly.

CRA and/or CDHS-18 Control
has foreign matter or mineral
buildup on yoke assembly.

CDHS-18 Control has foreign
matter or mineral buildup
above diaphragm.

Diaphragm of either control
leaks or stuck. Diaphragm
nut loose.

Clogged restriction assembly.

Clogged Flow Clean Strainer.

Control line shutoff cock from
inlet to restrictor closed.

CV Flow Control closed or
clogged.

Pilot control (CRA or
CDHS-18) disc worn or
nicked. Fails to seat.

REMEDY

Readjust controls.

Remove line and clean
orifice port. Clean or
replace line.

Open shutoff cock.

Remove plug and disc
retainer assembly. Clean
or replace.

Disassemble valve, clean
parts and/or replace dam-
aged parts.

Readjust controls.

Disassemble and clean
parts.

Disassemble and clean
parts.

Disassemble and clean
parts.

Remove and clean.

Remove and clean or
replace.

Open shutoff cock.

Readjust or disassemble
and clean.

Remove disc retainer
assembly and replace.

COVER

PIPE PLUG

COVER BEARING

SPRING

STEM NUT

DIAPHRAGM WASHER

DISC RETAINER

BODY

*

SPACER WASHERS

DISC GUIDE

SEAT

PIPE PLUG

STEM

SEAT O-RING

STUD

8" and Larger

*

DIAPHRAGM

*

DISC

*

Repair Parts

Seat Screw

8" and Larger

(Globe

or

Angle)

PIPE PLUG

HEX NUT

8" and Larger

Cover Bolt

6" and Smaller

D1

2

3

5

Y

B1

1

A

C

B1

S

D2

D3

B1

B2

4

INLET

OUTLET

X58C

CRA

X52A-1

X46A

2.

3.

CDHS18

5.

4.

A.

CK2

B.

1.

HYTROL MAIN VALVE

CV

C.

X43

Y.

For a more detailed IOM Manual go to www.cla-val.com or contact a Cla-Val Regional Sales Office.

40-01/640-01 SCHEMATIC

CDC-1

D.

Flow

BASIC COMPONENTS
1 100-01 Hytrol (Main Valve)

100-20 600 Series Hytrol (Main Valve)

2 X58C Restriction Fitting
3 CRA Pressure Reducing Control
4 X52A-1 Orifice Plate Assembly
4 CDHS18 Differential Control

OPTIONAL FEATURES
A X46A Flow Clean Strainer
B CK2 Valve (Isolation Valve)
C CV Flow Control (Closing)
D Check Valves with Isolation Valve
S CV Flow Control (Opening)
Y X43 “Y” Strainer

X140-1

Security Cap

Option