Extron Electronics SCP 100 Control Pad User Guide User Manual
Page 8
System 5
cr
• SCP 100 User’s Manual • Extron
Installation
Making Cables
Extron provides the 3.5 mm captive screw connectors with the
SCP-100, however a cable will have to be made to fit your
installation requirements. Wire the cable to be used between the
System 5 connector marked Aux1 or Aux2 (rear panel) and the
SCP 100 for a one-to-one configuration (wire pin #1 of one
connector to pin #1 of the other, #2 to #2, etc.) The contact
assignments are shown in Figure 1-5. Both ends of the cable use
a 3.5 mm, captive screw connector. No soldering is required for
this connector, simply insert the wires as shown in Figure 3 and
tighten the screws.
___ The maximum cable length for an SCP 100 to System 5 application
is 300 feet (91.4 meters).
Figure 1-5. Contact assignments for SCP 100 to System 5 connections
Testing the SCP 100
When finished, either end of the cable can plug to either device.
However, because there will be +12 volts from the System 5, it is
best to plug the cable to the SCP 100 first, and then to the
System 5. There is no setup procedure for this device. Proceed
with the operation of the panel(s) to verify that it is working
properly.
__ The IR 40 remote can be used from a distance of up to 100 feet
(30.5 meters) from the SCP 100 IR port.
1-3