CONDENSATE LINE

Important: Do not run the condensate drain in areas

that are likely to freeze. Frozen condensate will block the

drain line and result in property damage or water heater

malfunction.

Condensate Trap Assembly

A condensate trap/drain stem assembly has been supplied

with the water heater and is located behind the access door

inside the base of the water heater. This assembly must be

installed between the water heater and the exhaust outlet

piping to ensure proper operation of the water heater. To

install, remove the slip-joint nut, stainless steel washer, and

O-ring from the trap assembly. Slip the nut, washer and

O-ring (in that order) over the stainless exhaust tubing and

slide them back near the base of the heater. Insert the trap

assembly over the tubing (see figure 3A accordingly) and

firmly hand-tighten (using a wrench will cause the O-ring to

seal improperly) the nut to form a water-tight seal between

the O-ring and the stainless exhaust tubing. When

tightened, the nut to heater base clearance should be 3/4”

(+/- 1/8”) tolerance (1.9 cm +/- 0.31 cm tolerance).
Note: The trap should be aligned so that the exhaust pipe

is in a vertical position close to the surface of the water

heater.

Figure 2: Minimum Clearance Locations

Back 0” (0 cm)

Sides: 4” (10.2 cm)
Min. for service

Front: 24”
(61 cm )
Min. for service

Top: 0” (0 cm)

Vent: 0”
(0 cm)

Sides: 4” (10.2 cm)
Min. for service

Clearances and Accessibility

Notice: Minimum clearances from combustible materi-

als are stated on the data plate located on the front of the

water heater.

The water heater is certified for installation on a

combustible

floor.

Important: If installing over carpeting, the carpeting must

be protected by a metal or wood panel beneath the water

heater. The protective panel must extend beyond the full

width and depth of the water heater by at least 3 inches

(7.62 cm) in any direction or if in a alcove or closet instal-

lation, the entire floor must be covered by the panel. The

panel must be strong enough to carry the weight of the

heater when full of water.
Figure 2 may be used as a reference guide to locate the

specific clearance locations. A minimum of 24 inches

(61 cm) of front clearance and 4 inches (10.2 cm) on each

side should be provided for inspection and service.

Figure 3A: 2” Condensation Trap Installation