beautypg.com

Inlet/outlet vent terminations, Standard horizontal termination, Alternative horizontal termination – John Wood Polaris Commercial High-Efficiency User Manual

Page 10: Figure 7: standard horizontal termination, Figure 8: alternate horizontal termination

background image

10

INLET/OUTLET VENT TERMINATIONS

Standard Horizontal Termination

When 3 inch pipe is used between the water heater and the

outside wall, reduce it to 2 inch pipe before penetrating the

wall. A maximum of 18 inches (45.7 cm) of 2 inch pipe may

be used between the 3 inch transition and the inside of the

wall (see figure 7).
The standard horizontal air inlet termination is a 2 inch

pipe which terminates at the exterior wall and utilizes a

coupling to prevent the pipe from being pushed back into the

structure. The standard horizontal exhaust outlet termination

is a 2 inch pipe which terminates 12 inches (30.5 cm) from

the outside wall. The air inlet must be located with respect to

the exhaust outlet as shown in figure 7 (bottom).
Install a drain tee assembly and trap in the inlet vent as close

to the water heater as possible. This is to drain any water

that may be in the combustion air pipe and prevent it from

entering the blower. Connect the trap drain line to a suitable

drain or downstream of the condensate trap of the water

heater.
Note: See “Venting Additional Polaris

®

Units” on Page 11

for correct terminations if installing more than one Polaris

®

gas water heater.

Alternative Horizontal Termination

The combustion air and exhaust terminations may be

raised up to 24 inches (61 cm) above the wall penetrations

if required for anticipated snow levels (see figure 8). The

two elbows shown in figure 8 are considered part of the

termination and should not be included when determining

the maximum allowable vent pipe length.
Note: See “Venting Additional Polaris

®

Units” on Page 11

for correct terminations if installing more than one Polaris

®

gas water heater.

(30.5 cm)

24”

(61 cm)

Max.

(76.2 cm)

Figure 7: Standard Horizontal Termination

3” (7.6cm) Max.

4” (10 cm)

Max.

4” (10 cm)

Max.

12” (30.5 cm)

2”

Coupling

12” (30.5cm) Min. Above

Grade or Anticipated

Snow Level. See

Note 4.

Notes:
1. Support Horizontal Pipe Every

Four Feet (1.2 m). Support Vertical

Pipe Every Six Feet (1.8 m).

2. When Using 3 Inch Pipe, Reduce To 2 Inches Before

Penetrating The Outside Wall.

3. 18 Inch (45.7 cm) Maximum When Using 3 Inch Pipe.
4. Increase The 12 Inch (30.5 cm) Minimum Above

Grade To Keep Terminal Openings Above Anticipated

Snow Levels.

5. Slope All Piping Down Toward the Water Heater as

Follows:

‡ ´3LSLQJVORSH´3HU)RRWPPSHUPHWHU

‡ ´3LSLQJVORSH´3HU)RRWPPSHUPHWHU

*

*

*

Figure 8: Alternate Horizontal Termination