Gas supply and piping, Gas requirements, Gas piping – John Wood Polaris Commercial High-Efficiency User Manual

Page 17: Gas pressure

background image

17

GAS SUPPLY AND PIPING

Gas Requirements

Read the data plate to be sure the water heater is made

for the type of gas being used. This information will be

found on the data plate located on the front of the water

heater. If the information does not agree with the type of

gas available, do not install or operate the water heater.

Call your dealer.
Note: An odorant may be added by the gas supplier to

the gas used by this water heater. This odorant may fade

over an extended period of time. Do not depend upon this

odorant as an indication of leaking gas.

Gas Piping

The gas piping must be installed according to all local and

state codes or in absence of local and state codes with the

“National Fuel Gas Code”, ANSI Z223.1 (NFPA 54)-current

edition. Canadian installations must be performed in

accordance with CAN/CSA-B149.1-current edition.

Note: If using a flexible gas connector, make sure its rating

tag matches or exceeds the input of the water heater.
Follow the instructions below and reference figure 19 for

gas piping installation.
1. Install a readily accessible manual shut-off valve in the

gas supply line as recommended by the local utility.

Know the location of this valve and how to turn off the

gas to this unit.

2. Install a drip leg as shown. The drip leg must be no

less than 3 inches (7.62 cm) long for the accumulation

of dirt, foreign material and water droplets.

3. Install a ground joint union between the water heater

and the manual shut-off valve. This is to allow easy

servicing.

4. Turn the gas supply on and check for leaks. Use a

chloride-free soap and water solution (bubbles forming

indicate a leak) or other approved method.

3” (7.62 cm)

Minimum

Figure 19: Gas Piping Installation

Gas Pressure

Important: The gas supply pressure must not exceed the

maximum supply pressure as stated on the water heater’s

data plate. Minimum supply pressure should also be

maintained per the data plate.

Explosion Hazard

Use a new AGA or CSA approved gas

supply line.
Install a shut-off valve.
Do not connect a natural gas water

heater to a L.P. Gas Supply.
Do not connect an L.P. gas water heater

to a Natural Gas Supply.
Failure to follow these instructions can

result in death, explosion, or carbon

monoxide poisoning.