Condensate line, Vent pipe system, Vent termination – John Wood Polaris Commercial High-Efficiency User Manual

Page 21: Water system piping, Gas supply and piping, Electrical connections

background image

21

INSTALLATION CHECKLIST
Water Heater Location

Requirements

… Centrally located with the water piping system. Located

as close to the gas piping and vent pipe system as pos-
sible.

…

Located indoors and in a vertical position. Protected

from freezing temperatures.

…

Proper clearances from combustible surfaces main-

tained and not installed directly on a carpeted floor.
Sufficient room to service the water heater.

…

Provisions made to protect the area from water dam-

age. Properly sized metal drain pan installed and piped
to an adequate drain.

…

Installation area free of corrosive elements and

flammable materials.

Condensate Line

… Drain stem is fully inserted in the elbow and glued

properly.

… Trap aligned so that the exhaust pipe is in a vertical

position close to the surface of the water heater.

… Line properly sloped to adequate drain or approved

condensate pump.

… Properly vented.
… Protected from freezing (if required).

Vent Pipe System

… Vent pipe and fittings of approved material.
… Acceptable size, length, and number of elbows on air

inlet pipe.

… Acceptable size, length, and number of elbows on

exhaust outlet pipe.

… Add the air inlet filter per the manufacturer’s instruction.
… Installed in accordance with prevailing provisions of

Local codes, or in the absence of such, National Fuel
Gas Code, NFPA 54, ANSI Z223.1-Current Edition.
Canadian Installations must be performed in accor-
dance with CAN/CSA-B149.1-Current Edition.

… All 2” horizontal piping sloped down toward the water

heater at 1/4” per foot (21 mm per meter). 3” piping
sloped down towards the heater at 1/8” per foot (10.5
mm per meter).

… Not obstructed in any way.

Vent Termination

Horizontal

… Correct relationship - outlet to inlet.
… 12” Min. (30.5 cm) above grade/snow level.
… 2” exhaust outlet/air inlet pipe sloped down towards

water heater at 1/4” per foot (21 mm per meter). 3”
piping sloped down towards the heater at 1/8” per foot
(10.5 mm per meter).

… Away from corners, other vents, windows, etc.

Alternate

Horizontal

… Correct relationship - outlet to inlet.
… 12” Min. (30.5 cm) above anticipated snow level.
… 2” exhaust outlet/air inlet pipe sloped down towards

water heater at 1/4” per foot (21 mm per meter). 3”

piping sloped down towards the heater at 1/8” per foot
(10.5 mm per meter).

… Away from corners, other vents, windows, etc.

Vertical

… Inlet - 12” Min. (30.5 cm) above roof/snow level.
… Correct relationship - outlet to inlet.
… Away from corners, other vents, windows, etc.

Concentric

… 12” Min. (30.5 cm) above grade/snow level.
… 2” exhaust outlet/air inlet pipe sloped down towards

water heater at 1/4” per foot (21 mm per meter). 3”
piping sloped down towards the heater at 1/8” per foot
(10.5 mm per meter).

… Away from corners, other vents, windows, etc.

Water System Piping

… Temperature and pressure relief valve properly

installed with a discharge line run to an open drain and
protected from freezing.

… All piping properly installed and free of leaks.
… Heater completely filled with water.
… A properly sized expansion tank must be installed on all

closed systems.

… A mixing valve must be installed per the manufacturer’s

instructions.

Gas Supply and Piping

… If using a flexible gas connector, make sure its rating

tag matches or exceeds the input of the water heater.

… Adequate pipe size and of approved material.
… Gas supply is the same type as listed on the water

heater data plate.

… Gas line equipped with full opening shut-off valve,

union and drip leg.

… Approved pipe joint compound used.
… Chloride-free soap and water solution or other ap-

proved means used to check all connections and fit-
tings for possible gas leaks.

Electrical Connections

… Unit connected to a dedicated power supply.
… Unit connected to a 120V electrical supply.
… Proper polarity.
… Water heater properly grounded.
… Installed in accordance with prevailing provisions of

local codes, or in the absence of such, National Fuel
Gas Code, NFPA 54, ANSI Z223.1-Current Edition.
Canadian installations must be performed in accor-
dance with CAN/CSA-B149.1-Current Edition.