beautypg.com

John Wood Atmospheric Gas (Standard) User Manual

Page 30

background image

30

PROBLEM

POSSIBLE CAUSE(S)

CORRECTIVE ACTION

SLOW HOT WATER

RECOVERY

1. Insufficient combustion air

2. Water heater flue or vent system

blocked

3. Low gas pressure

4. Improper

calibration

5. Base-Ring Filter blocked with lint/

dust

6. FVIR Flame Arrestor blocked with

lint/dust.

1. Provide ventilation to water heater. Check

flue way, flue baffle, and burner

2. Clean flue, locate source and correct

3. Check with gas utility company

4. Replace

thermostat

5. Clean filter, See “External Inspection &

Cleaning of the Base-Ring Filter” section.

6. Clean filter, See “Cleaning the Combustion

Chamber and Flame-Arrestor” section.

DRIP FROM RELIEF VALVE

1. Excessive water pressure

2. Heater

stacking

3. Closed water system

1. Use a pressure reducing valve and relief

valve

2. Lower the thermostat setting

3. See “Closed System/Thermal Expansion”

THERMOSTAT FAILS TO

SHUT-OFF

1. Thermostat not functioning prop-

erly

2. Improper

calibration

1. Replace

thermostat

2. Replace

thermostat

COMBUSTION ODORS

1. Insufficient combustion air

2. Water heater flue or vent system

blocked

3. Heater installed in a confined area

4. Base-Ring Filter blocked with lint/

dust

5. FVIR Flame Arrestor blocked with

lint/dust.

1. Provide ventilation to water heater. Check

flue

way, flue baffle, and burner

2. Clean, locate source and correct

3. Provide fresh air ventilation

4. Clean filter, See “External Inspection &

Cleaning of the Base-Ring Filter” section.

5. Clean filter, See “Cleaning the Combustion

Chamber and Flame-Arrestor” section.

SMOKING AND CARBON

FORMATION (SOOTING)

1. Insufficient combustion air

2. Low gas pressure

3. Water heater flue or vent system

blocked

4. Thermostat not functioning prop-

erly

5. Heater installed in a confined area

6. Burner flame yellow-lazy

7. Base-Ring Filter blocked with lint/

dust

8. FVIR Flame Arrestor blocked with

lint/dust.

1. Provide ventilation to water heater. Check

flue way, flue baffle, burner

2. Check with gas utility company

3. Clean, locate source and correct

4. Replace

thermostat

5. Provide fresh air ventilation

6. See “Burner Flame Yellow-Lazy”

7. Clean filter, See “External Inspection &

Cleaning of the Base-Ring Filter” section.

8. Clean filter, See “Cleaning the Combustion

Chamber and Flame-Arrestor” section.

CONDENSATION

1. Temperature setting too low

1. Increase the temperature setting. Refer

to the “Condensation” sub-section of this

manual’s Troubleshooting Guide.

BURNER FLAME FLOATS

AND LIFTS OFF PORTS

1. Orifice too large

2. High gas pressure

3. Water heater flue or vent system

blocked

4. Cold

drafts

1. Replace with correct orifice

2. Check with gas utility company

3. Clean flue and burner-locate source and cor-

rect

4. Locate source and correct

BURNER FLAME TOO HIGH

1. Orifice too large

1. Replace with correct orifice

FLAME BURNS AT ORIFICE

1. Thermostat not functioning prop-

erly

2. Low gas pressure

1. Replace

thermostat

2. Check with gas utility company

PILOT FLAME

TOO SMALL

1. Pilot line or orifice clogged

2. Low gas pressure

1. Clean, locate source and correct

2. Check with gas utility company