beautypg.com

Piezoelectric igniter system, Testing the igniter system – John Wood Atmospheric Gas (Standard) User Manual

Page 28

background image

28

7. Connect the white and red wires to the gas control

valve/thermostat as shown in Figure 21. Also, ensure

that the red thermal switch wires are connected to the

thermal switch on the manifold door..

8. Reconnect the igniter wire (Figure 20).
9. Turn on the gas supply to the water heater at the manual

gas shut-off valve (Figure 3).

10. Follow the lighting instructions on the front of the water

heater. With the main burner lit, check for leaks at
the manifold and pilot connections by brushing on an
approved noncorrosive leak detection solution. If such
a solution is not available, use a mixture of hand dish
washing soap and water (one part soap to 15 parts
water) or childrens’ soap bubble solution. Bubbles
forming indicate a leak. Correct any leak found.

11. Verify proper operation, then replace the outer door.

MANIFOLD TUBE

TIP

BRACKET

SLOT

CLOSE-UP INSIDE VIEW OF

THE COMBUSTION CHAMBER.

FIGURE 27.

Piezoelectric Igniter System

The piezoelectric igniter system consists of the igniter
button, electrode, and wire. The pilot is ignited by an
electric spark generated when the igniter button is pressed.
(See Figure 28).

VAC

PILOT/
THERMOPILE
BRACKET

ELECTRODE

THERMOPILE

PILOT

IGNITER BUTTON

WIRE TO ELECTRODE

FIGURE 28.

Testing the Igniter System

Turn off the gas to the water heater at the manual gas

shut-off valve. Watch the electrode tip while activating the

igniter. A visible spark should jump from the electrode. To

avoid shock, do not touch the burner or any metal part

on the pilot or pilot assembly. If no spark is visible, check

the wire connections and make sure the electrode is not

broken. Replace the igniter if defective. Dirt and rust on the

pilot or electrode tip can prevent the igniter spark. Wipe

clean with a damp cloth and dry completely. Rust can be

removed from the electrode tip and metal surfaces by

lightly sanding with an emery cloth or fine grit sandpaper.

Removing and Replacing the Gas Control
Valve/Thermostat

IMPORTANT: This water heater has a resettable thermal
switch installed. Do not attempt to disable or modify this
feature in any way. Use only factory authorized

replacement parts.
Removing the Gas Control Valve/Thermostat:
1. Turn the gas control/temperature knob to the “OFF”

position (Figure 17A).

2. Turn off the gas at the manual shut-off valve on the gas

supply pipe (Figure 3).

3. Drain the water heater. Refer to the section of “Draining

and Flushing” and follow the procedure.

4. Disconnect the igniter wire from the igniter lead wire.

Use needle nose pliers to disconnect the red (+) and
white (-) thermopile wires. Disconnect the pilot tube
(SAE 7/16” wrench) and manifold tube (SAE 3/4”
wrench) at the gas control valve/thermostat (Figure 20).
NOTE: L.P. Gas systems use reverse (left-hand) threads
on the manifold tube.

5. Refer to “Gas Piping” (Figure 3) and disconnect the

ground joint union in the gas piping. Disconnect the
remaining pipe from the gas control valve/thermostat.

6. To remove the gas control valve/thermostat, thread

a 4” (10.2 cm) section of gas pipe into the inlet
and use it to turn the gas control valve/thermostat
(counterclockwise.) Do not use a pipe wrench or
equivalent to grip body. Damage may result, causing
leaks. Do not insert any sharp objects into the inlet or
outlet connections. Damage to the gas control valve/
thermostat may result.

Replacing the Gas Control Valve/Thermostat:
To replace the gas control valve/thermostat, reassemble

in reverse order. When replacing the gas control valve/
thermostat, thread a 4” (10.2 cm) section of gas pipe into

the inlet and use it to turn the gas control valve/thermostat

(clockwise). DO NOT OVER TIGHTEN; damage may result.

Be sure to use approved Teflon® tape or pipe joint

compound on the gas piping connections and fitting on

the back of the gas control valve that screws into the tank.

Be sure to remove the pilot ferrule nut from the new gas

control valve/thermostat.

Turn the main gas supply on and check the gas supply

connections for leaks. Correct any leak found.

Next, light the pilot and main burner, then check the

manifold tube and pilot tube connections for leaks.

Correct any leak found.

Use an approved noncorrosive leak detection solution.

If such a solution is not available, use a mixture of

hand dish washing soap and water (one part soap

to 15 parts water) or childrens’ soap bubble solution.

Bubbles forming indicate a leak.

Be sure tank is completely filled with water before

lighting and activating the water heater. Follow the

“Lighting Instructions” on page 20.

If additional information is required, reference the number

on the cover of this manual for service information.

TEFLON

®

is a registered trademark of E.I. Du Pont De Nemours and Company