beautypg.com

John Wood Atmospheric Gas (Standard) User Manual

Page 29

background image

29

FVIR System Operational Checklist

1. Manifold gasket properly sealed.
2. Viewport not damaged or cracked.
3. Flame-arrestor free of debris and undamaged.
4. Manifold component block properly installed.

5. No leaks at pilot and manifold connection.
6. Manifold door screws securely tightened.
7. Depress the button on the thermal switch

TROUBLESHOOTING CHART

PROBLEM

POSSIBLE CAUSE(S)

CORRECTIVE ACTION

BURNER WILL NOT IGNITE

1. Pilot not lit

2. Thermostat set too low

3. Main burner line clogged

4. Non-functioning

thermostat

5. Base-Ring Filter blocked with lint/

dust

6. Heater installed in a confined area

7. FVIR Flame Arrestor blocked with

lint/dust.

1. Light

pilot

2. Turn temp. dial to desired temperature

3. Clean, locate source and correct

4. Test Gas Control Valve/Thermostat

5. Clean filter, See “External Inspection &

Cleaning of the Base-Ring Filter” section.

6. Provide fresh air ventilation

7. Clean filter, See “Cleaning the Combustion

Chamber and Flame-Arrestor” section.

SMELLY WATER

1. Sulfides in the water

1. Replace the anode with a special anode

BURNER FLAME YELLOW-

LAZY

1. Insufficient combustion air

2. Low gas pressure

3. Water heater flue or vent system

blocked

4. Main burner line clogged

5. Base-Ring Filter blocked with lint/

dust

6. Heater installed in a confined area

7. FVIR Flame Arrestor blocked with

lint/dust.

8. Obstruction in main burner orifice

1. Provide ventilation to water heater

2. Check with gas utility company

3. Clean, locate source and correct

4. Clean, locate source and correct

5. Clean filter, See “External Inspection &

Cleaning of the Base-Ring Filter” section.

6. Proper fresh air ventilation

7. Clean filter, See “Cleaning the Combustion

Chamber and Flame-Arrestor” section.

8. Clean or replace orifice

PILOT WILL NOT LIGHT OR

REMAIN LIT

1. Non-functioning

igniter

2. The thermal switch tripped

3. Wire lead connection at thermal

switch loose

4. Thermopile connection loose

5. Air in gas line

6. Low gas pressure

7. No

gas

8. Dirt in gas lines

9. Cold

drafts

10. Thermostat temperature limit was ex-

ceeded. Status light will blink 4 flashes.

11. Pilot line or orifice clogged

12. Non-functioning thermopile

13. Air for combustion obstructed

14. FVIR Flame Arrestor blocked with

lint/dust

15. Flammable vapors incident, FVIR

function actuated

16. Base-Ring Filter blocked with lint/

dust

1. Replace igniter pilot assembly

2. See Pilot Light Troubleshooting Flowchart section

3. Remove and reconnect the wire leads at

thermal switch, confirm connections are tight

and not loose

4. Finger tighten; then 1/4 turn with wrench

5. Bleed the air from the gas line

6. Check with gas utility company

7. Check with gas utility company

8. Notify utility-install dirt trap in gas line

9. Locate source and correct

10. Replace thermostat

11. Clean, locate source and correct

12. Replace thermopile

13. See maintenance section for inspection and

cleaning of flame arrester

14. Clean filter, See “Cleaning the Combustion

Chamber and Flame-Arrestor” section.

15. Replace water heater, eliminate flammable

vapors source. Contact Technical Assistance.

16. Clean filter, See “External Inspection &

Cleaning of the Base-Ring Filter” section.

HIGH OPERATION COSTS

1. Thermostat set too high

2. Sediment or lime in tank

3. Water heater too small for job

4. Wrong piping connections

5. Leaking

faucets

6. Gas

leaks

7. Wasted hot water

8. Long runs of exposed piping

9. Hot water piping in exposed wall

1. Set temperature dial to lower setting

2. Drain/flush-provide water treatment if needed

3. Install adequate heater

4. Correct piping-dip tube must be in cold inlet

5. Repair

faucets

6. Check with utility-repair at once

7. Advise

customer

8. Insulate

piping

9. Insulate

piping

INSUFFICIENT HOT WATER 1. Thermostat set too low

2. Sediment or lime in tank

3. Water heater too small

4. Wrong piping connections

5. Leaking

faucets

6. Wasted hot water

7. Long runs of exposed piping

8. Hot water piping in outside wall

9. Low gas pressure

1. Turn temperature dial to desired setting

2. Drain/flush-provide water treatment if needed

3. Install adequate heater

4. Correct piping-dip tube must be in cold inlet

5 Repair

faucets

6. Advise

customer

7. Insulate

piping

8. Insulate

piping

9. Check with gas utility company