Sdi-12 command & response – Xylem SDI-12 RADAR User Manual

Page 32

background image

xx...xx

is an optional field of up to a maximum of 13 characters to be used for serial number

or other specific sensor information not relevant to operation of the data recorder.

SDi-12 CommaND & reSPoNSe

30

example of a “aI!” command:

“a12 Daa H-3611vvvS#nnnnnnVkkk

radar implementation of the optional 13 character field:

S#nnnnnnVkkk

(12 bytes total)

where:

“nnnnnn

is a six character sensor serial number

“kkk”

is a three digit sensor firmware revision level

The Change Sensor address Command allows the sensor address to be changed. The address is

stored in non-volatile eeProm within the sensor. The radar will not respond if the command was

invalid, the address was out of range, or the eeProm programming operation failed.

Command

response

Description

“aan!

“n

Change sensor address

where:

a

is the current (old) sensor address (“0-9”, “a-Z”, “a-z”, “*”, “?”). an aSCii “*” may be used

as a “wild card” address if the current address is unknown and only one sensor is

connected to the bus.

a

is an upper-case aSCii character.

n

is the new sensor address to be programmed (“0-9”, “a-Z”).

NoTe: To verify the new address use the “identify Command.”

Change Sensor address Command

example of a “Change sensor address” command:

Command

response

Description

“aa2!

“2

Change sensor address to “2”