4 connection diagram, 5 i/o description, 1 external start/stop – Xylem ECOCIRC XL, XLplus Electronic drive User Manual

Page 5: 2 external analog input 0-10v, 3 fault signal

background image

- Analog 0-

10V

- External

pressure
sensor

- External

temperature
sensor

- External

start/stop

If NO fault
signal on
this cable
gland
.
Multi-wire
control
cable,
number of
wires
according
to number
of control
circuits.
Shielded if
necessary

Multi-wire
control
cable,
number of
wires
according
to number
of control
circuits.
Shielded if
necessary

Communicati
on bus

Bus cable

Table 3

2.4 Connection diagram

With reference to

Figure 8

and

Figure 9

:

Function

Terminal

pair

Contact rating

See

par.

External
start/stop



The drive
provides 5VDC
through these
terminals: no
external voltage
must be
provided!

2.5.1

0-10V external
analog input



2.5.2

Fault signal



Max 250V at 2A
(inductive load)

2.5.3

4-20mA
pressure sensor
input



2.5.4

External
temperature
sensor

4



The drive works
with a KTY83
temperature
sensor (1K

Ω at

25°C)

2.5.5

Communication
bus (standard)

4



TIA/EIA RS485

2.5.6

Communication
bus (optional)

4



TIA/EIA RS485

2.5.7

Optional
Wireless /
RS485 module



2.5.8

Table 4

2.5 I/O description

2.5.1 External start/stop []

The circulator can be started or stopped via an
external potential-free contact or a relay connected to
terminals

and

. If no external start/stop switch is

connected, the connection jumper between terminals

4

Only on ecocirc XLplus

and

, which is the factory setting, should be

maintained.

NOTICE
The drive provides 5VDC through these terminals: no
external voltage must be provided to these terminals!

2.5.2 External analog input 0-10V []

An external analog signal 0-10V, applied to terminals

and

, controls the circulator speed in a range from

0 to 100%, following a linear function as depicted in

Figure 1

.

Figure 1


In the below table a description of the milestones
shown in

Figure 1.

V

in

thres

holds

[V]

Speed

setpoint

[rpm]
when

V

in

Pump

status

when V

in

Po
int

Speed

setpoint

[rpm]
when

V

in

Pump

status

when V

in

Po
int

0

-

Input

disabled

-

-

Input

disabled

-

0.8

-

Input

disabled

-

0

OFF

1.19

-

Input

disabled

-

0

OFF

1.20

0

OFF

MIN

RUN

1.49

0

OFF

MIN

RUN

1.50

MIN

RUN

MIN

RUN

10.0

MAX

RUN

MAX

RUN

Table 5

2.5.3 Fault signal []

The drive controls a relay for a potential-free fault
signal: in case of blocking error, the relay is activated
so that the terminals

and

are short circuited.


RATINGS
V

max

< 250VAC

I

max

< 5A (if resistive load)

I

max

< 2A (if inductive load)