5 Fault finding
Referring to
models) and to
connected models), as briefly described in par. 4.1
In case of any alarm that allows the pump
to continue running, the display shows
alternatively alarm code (see par. 5.1) and
last quantity selected, while the status
indicator becomes orange
In case of a failure that stops the pumps,
the display shows the error code (see par.
5.2) permanently and the status indicator
becomes red
5.1 Alarm codes
Alarm
code
Description
Cause
A01
Water probe alarm
Fluid sensor
anomaly
A02
Water over-temperature
alarm
High temperature
on the fluid
A05
Data memory alarm
Data memory
corrupted
A06
External water temp.
probe alarm
External
temperature probe
anomaly
A07
Pressure sensor alarm
External pressure
sensor anomaly
A12
Twin pump
communication alarm
Twin pump
communication
lost
A20
Internal alarm
5.2 Error codes
Error
code
Description
Cause
E01
Internal communication
error
Internal
communication
lost
E02
Motor overload error
High motor current
E03
DC-bus overvoltage error
DC-bus
overvoltage
E04
Trip control error
Motor stall
E05
EEPROM Data memory
error
EEPROM Data
memory corrupted
E06
Grid voltage error
Voltage supply out
of operating range
E07
Motor winding
temperature error
Motor thermal
protection trip
E08
Power module
temperature error
Inverter thermal
protection trip
E09
Generic Hardware error
Hardware error
E10
Dry-run error
Dry run detection