beautypg.com

Bell & Gossett S14141B 70X Multiple Pump Pressure Booster Systems User Manual

Page 8

background image

SECTION 4 - MAINTENANCE

4.1 MAINTENANCE (PHYSICAL)

4.1.1

Refer to specific component IOM for maintenance
information.

4.1.2

Mechanical - A Series 1531 pump was lubricated
at the factory. Future lubrication should be accord-
ing to the motor manufacturer’s instructions.

4.1.3

A Series 1510 pump requires regreasing after
every 2500 hours of operation or every six months
whichever occurs first. Lubricate motor per motor
manufacturer’s instruction.

4.1.4

If there is a danger of freezing, drain the pump.
Inspect pump and system piping regularly.

4.1.5

For leaky seals or gaskets and loose or damaged
components, replace or repair as required.

For more instruction on the B&G pumps see the following

manuals: 1510 (IOM Part #P81673) or 1531 (IOM Part
#P81567).

8