Programming – Xylem IM098 AQUAVAR Model 56 Controller User Manual
Page 19

To set run out protection:
Note
Run out protection occurs if the pump is running at full speed, and the set pressure cannot be
recorded after a set period of time. To set run out protection you need to enter the amount of
pressure drop and the time delay.
Instructions
1) Password The password protection prevents
untrained personnel from accidentally changing
the base setting.
• From the parameter screen on the main menu
press the arrow until the display changes to:
2) Press the arrow until you reach the number
0066.
3) Press the ➔ arrow repeatedly until you reach:
4) Press the arrow once and you will reach:
5) By pressing the arrow. Enter the pressure
setting (in psi) at which you want the pump to
shutoff. Typically a setting of 3 to 5 psi less
than the standard pressure setting would be
entered.
6) Now press the ➔ arrow and you will reach:
7) By pressing the arrow you will be entering
the amount of time (in seconds) that the pump
will run at the pressure setting programmed
into the conveyor limit before it automatically
shuts off. Returning to normal operation:
8) Hold the ➔ arrow down for 3 seconds and you
will be returned to:
9) Hold the ➔ arrow down again for 3 seconds
and you will be returned to: The Main Menu.
Programming
14
CONVEYOR LIMIT
0.0 PSI
CONVEYOR LIMIT
25 PSI
ERROR DELAY
0S
➔
➔
ERROR DELAY
5S
SUBMENU
ERROR
PASSWORD
0000
PASSWORD
0066
SUBMENU
ERROR
➔
➔
PRESSURE 00 PSI
SPEED 00HZ
➔