OPERATION AND MAINTENANCE

Operators must be familiar with all sections of this manual

to understand the operation of the unit.

Hot Water, steam and electricity can be hazardous.

NOTICE / AUTO RESTART

Single phase motors will restart automatically after thermal

overload protector trips.

A properly installed unit should function unattended for

long periods of time. Periodic checks to assure proper

operation are highly recommended. Refer to trouble shoot-

ing section when necessary.

Refer to wiring diagrams to determine control switch

settings.

UNIT WIRING

Select the required configuration for the control panel to fit

the application.

CAUTION: Verify that the incoming voltage

and the motor voltage correspond to the configuration of

the panel. Rewire jumper terminals if necessary.

Disconnect all power.

Identify incoming power and motor voltage configuration

from the Selection Chart below.

DESCRIPTION

The Hoffman Single Phase Simplex Electrical Control

Panel is designed to provide a reliable means of controlling

one 120 volt or 230 volt (3 wire) single phase pump instal-

lation that

does not exceed a FLA of 20 amps.

PRELIMINARY INSPECTION

Assure that there is no shipping damage.

Assure that the nameplate ratings agree with the job spec-

ifications and actual conditions.

Assure all connections are secure and made per NEC

requirements.

HANDLING

Use care in installing unit.

LOCATION

Place unit for easy access.

Allow adequate space for servicing. Check ambient

conditions.

Notice: Insulation temperature limits. Ventilate as required.

ELECTRICAL WIRING AND CONTROLS

Connect power wiring per NEC. Recheck nameplate vs.

specifications and conditions.

PUTTING THE UNIT INTO SERVICE

Assure that the main power has been disconnected.

Wire unit per National Electrical Code. See representative

wiring diagrams.

Observe operation of unit through several cycles.

SELECTION CHART

Incoming

Motor

Connect Power

Connect Pump Motor

Jumper

Connect Float Control

Voltage

Voltage

to Terminals

to Terminals

Terminals

to Terminals

230/1/60

230/1/60

N, L2, L1

T1, T2

L1, 2

115/1/60

115/1/60

L2, L1

T1, T2

N, L2

L1, 2

2

WARNING: HIGH VOLTAGE ELECTRICITY

Disconnect and lock out power before connecting or

servicing unit. Failure to follow these instructions could

result in serious injury or death.

WARNING: HIGH VOLTAGE ELECTRICITY

Disconnect and lock out power before connecting or

servicing unit. Failure to follow these instructions could

result in serious injury or death.

WARNING: HIGH VOLTAGE ELECTRICITY

Disconnect and lock out power before connecting or

servicing unit. Failure to follow these instructions could

result in serious injury or death.

CAUTION: SUBSEQUENT DAMAGE

A unit showing symptoms of possible problems must

be corrected immediately. Failure to follow these instruc-

tions could result in full liability for subsequent injury or

property damage.

SAFETY INSTRUCTIONS

See Cover of this Manual.

WARNING: HIGH VOLTAGE ELECTRICITY

Disconnect and lock out power before connecting or

servicing unit. Failure to follow these instructions could

result in serious injury or death.