SERVICE INSTRUCTIONS
The strainer in the R series Rolairtrol may need to be cleaned periodically. This is
particularly true during the initial start-up period. The need to clean the strainer
will be evidenced by a high pressure drop across the Rolairtrol or by pump cavi-
tation problems. To clean the strainer:
a) Allow the system water temperature to cool below 100°F.
b) Open the blowdown drain valve for a few seconds. This should dislodge
accumulated dirt from the strainer. If it does not then the strainer must be
removed from the Rolairtrol for cleaning. This can be accomplished by clos-
ing the isolation valves to isolate the Rolairtrol from the system. Make sure
the water temperature in the Rolairtrol is below 100°F. Open the blowdown
valve on the bottom of the Rolairtrol to drain the unit. Make sure that all flow
from the blowdown valve has stopped. If water continues to flow, the isola-
tion valves must be repaired or replaced before proceeding.
c) For 2", 2
1
/
2
" and 14" through 24" models, remove the flange bolts that hold
the strainer housing cover in place on the bottom of the Rolairtrol. Remove the
cover and strainer. Clean the strainer and reinstall in the Rolairtrol. Replace
the cover gasket with a new one and reinstall the cover making sure that the
flange bolts are tightened in a criss-cross pattern to the proper torque. Close
the blowdown valve and open the isolation valves to return the Rolairtrol to
normal operation. Check the gasket for signs of leakage. If found, additional
slight tightening of bolts may be required.
d) For 3" through 12" of the R models, remove the 3" pipe plug that holds the
strainer in place on the bottom of the Rolairtrol. Remove and clean the strainer,
reinstall them making sure that the strainer goes through the strainer guide
and the pipe plug is tightened. Close the blowdown valve and open the isola-
tions to return the Rolairtrol to normal operation. Check the pipe plug for
signs of leakage. If found, additional slight tightening of pipe plug may be
required.
e) Do not use any open flame devices (torches, solder guns, etc.) which may
thermally degrade the painted or galvanized surfaces and cause the release
of harmful decomposition products, which may be harmful if breathed.
WARNING: Leakage, corrosion or indications of damage are signs of
an impending serious failure of the Rolairtrol. Periodically inspect for
damage and if noted the Rolairtrol must be serviced or replaced. Failure to
follow these instructions could result in serious personal injury or death
and property damage.
WARNING: System fluid under pressure and/or high temperature
can be very hazardous. Before proceeding to service strainer, reduce
system pressure to zero or isolate the Rolairtrol from the system. Allow the
system to cool below 100°F. Failure to follow these instructions could
result in serious personal injury or death and property damage.
CAUTION: The use of Teflon
®
* impregnated pipe compound and
Teflon
®
tape on pipe threads provides lubricity which can lead to
overtightening and breakage. Do not overtighten. Failure to follow this
instruction can result in moderate personal injury from hot water and/or
property damage.
WARNING: Water at temperatures above 100°F can be very
hazardous. Allow system water temperature to cool down below
100°F before blowing down Rolairtrol. Failure to follow these instructions
could result in serious personal injury or death and property damage.
WARNING: Failure to follow these instructions could result in serious
personal injury or death.
TYPICAL HYDRONIC HEATING/COOLING APPLICATIONS
Fig. 1 Air Control
Fig. 2 Air Elimination
WARNING: The use of improper mating flanges, connectors, gaskets
or bolting can cause flange or connector failure resulting in the loss
of hot or cold system fluid. Use only companion cast iron ANSI flanges or
connectors with appropriate gaskets and properly tightened bolts. Failure
to follow this instruction can result in serious personal injury and/or prop-
erty damage.
*Teflon is a registered trademark of E.I. DuPont de Nemours and Company.
Xylem Inc.
8200 N. Austin Avenue
Morton Grove, Illinois 60053
Phone: (847) 966-3700
Fax: (847) 965-8379
www.xyleminc.com/brands/bellgossett
Bell & Gossett is a trademark of Xylem Inc. or one of its subsidiaries.
© 2012 Xylem Inc. A85524C May 2012