INST

ALLATION INSTRUCTIONS

Enhanced Air Separators with Sweat Connections

1.

Install the air separator in horizontal piping so that the air

vent is in the top vertical position. The air separator is

bi-directional so that water can flow in either direction

(see Figure 1).

2. Use a torch with a sharp pointed flame.
3. Clean tube ends and air separator connection thoroughly.
4. Use 95-5 (Tin-Antimony) solder and a good grade of flux.

5. When sweating joints, first wrap the air separator with a cool

wet rag, then direct the flame with care to avoid subjecting

the EASB-JR to excessive heat.

6. Refer to Chart A for the maximum operating pressure and

temperature based on the type of solder used.

7. After sweating the joints, check the connections for leakage.

Enhanced Air Separators with NPT

Connections

1.

Install the air separator in horizontal piping so that the air

vent is in the top vertical position. The use of Teflon tape

sealer or a high quality thread sealant is recommended. The

air separator is bi-directional so that water can flow in either

direction (see Figure 1).

2. Check connections for leaks.

OPERA

TING INSTRUCTIONS

T

urn the cap on top of the vent counterclockwise one full turn to

allow the EASB-JR to automatically remove the air from the

system. This is the normal operating position.
To shut down the automatic air vent, turn the cap tight. Be sure

to turn the cap back to the open position (one full turn) for

normal operation.

SER

VICE INSTRUCTIONS

The Enhanced Air Separator should not r

equire servicing. If the

system fluid contains large amounts of contaminants, the

perforated metal strainer may become contaminated with

foreign substances. The Enhanced Air Separator cap unscrews

from the body for easy cleaning of strainer.

CAUTION: The use of T

eflon

®

impregnated pipe com-

pound and Teflon tape on pipe threads provides lubricity

which can lead to overtightening and breakage. Do not over-

tighten. Failure to follow this instruction can result in moder-

ate personal injury from hot water and/or property damage.

CAUTION: Contaminants and scale fr

om the system

can foul the automatic air vent operation mechanism.

Keep vent cap closed tight during the system filling to pre-

vent contaminants from running into valve vent mechanism.

Failure to follow these instructions could result in property

damage and/or moderate personal injury.

W

ARNING:

Servicing the Enhanced Air Separator with

unit pressurized or at temperatures above 100°F

(37.8°C) can cause personal injury. Make sure pressure is

removed from unit and temperature is below 100°F (37.8°C).

Failure to follow these instructions could result in serious

personal injury or death and property damage.

RETURN

OPTIONAL SIDE

OUTLET BOILER

CONNECTION

TYPICAL INSTALLATION – FIGURE 1

DIAPHRAGM TYPE

EXPANSION TANK

TO

SYSTEM

FLO-CONTROL

VALVE

B&G BOOSTER

EASB-JR AIR

SEPARATOR

B&G PRESSURE

REDUCING VALVE

SHUT-OFF

VALVE

CW FILL

B&G RELIEF

VALVE

FLOW

BOILER

CAUTION: Heat associated with the use of silver solder

may damage a Air Separator voiding the warranty. Do

not use silver solder. Failure to follow these instructions could

result in proper damage and/or moderate personal injury.

CAUTION: Hot venting can be hazar

dous. Avoid con-

tact with venting fluid and only manually vent when

system temperature is below 100°F (38°C). Failure to follow

these instructions could result in property damage and/or

personal injury.

W

ARNING: State of California Residents

This pr

oduct contains a chemical known by the State

of California to cause cancer. This product contains a chemi-

cal known by the State of California to cause birth defects or

other reproductive harm.

CAUTION: Uncontr

olled venting of water can occur

with automatic air vents if foreign material prevents

vents from closing. Unwanted flow should be directed to a

drain. Failure to follow these instructions could result in prop-

erty damage and/or moderate personal injury.

Xylem Inc.

8200 N. Austin Avenue

Morton Grove, Illinois 60053

Phone: (847) 966-3700