Display

Fault

Notes

OUTDOOR

The control is no longer able to read the outdoor sensor due to an open circuit. In this

SENSOR OPEN

case, the control assumes an outdoor temperature of 32°F (0°C) and continues operation.

CIRCUIT

Check wiring between outdoor sensor and control unit. Verify all connections and inspect

for broken wire or damaged sensor. To clear the error message from the control after

the sensor has been repaired, press the Item button

BOILER

The control is no longer able to read the boiler sensor due to a short circuit. In this

SENSOR

case, if the BOIL MIN adjustment is set to OFF the control does not operate the Boiler

SHORT

contact. If the BOIL MIN adjustment is not set to OFF and a boiler demand is present,

CIRCUIT

the Boiler contact will operate for up to 10 minutes of a 20 minute cycle. Check wiring

between outdoor sensor and control unit. Verify all connections and inspect wire

insulation and sensor for damage. To clear the error message from the control after

the sensor has been repaired, press the Item button

BOILER

The control is no longer able to read the boiler sensor due to a open circuit. In this

SENSOR

case, if the BOIL MIN adjustment is set to OFF, the control does not operate the Boiler

OPEN

contact. If the BOIL MIN adjustment is not set to OFF, and a boiler demand is present,

CIRCUIT

the Boiler contact will operate for up to 10 minutes of a 20 minute cycle. Check wiring

between outdoor sensor and control unit. Verify all connections and inspect wire

insulation and sensor for damage. To clear the error message from the control after

the sensor has been repaired, press the Item button

MIX SENSOR

The control is no longer able to read the mixing sensor due to a short circuit. In this

SHORT CIRCUIT

case, the control will operate the injection pump at a fized output as long as there is a

mixing demand. Check wiring between sensor and control unit. Verify all connections

and inspect wire insulation and sensor for damage. To clear the error message from the

control after the sensor has been repaired, press the Item button

MIX SENSOR

The control is no longer able to read the mixing sensor due to a open circuit. In this

OPEN CIRCUIT

case, the control will operate the injection pump at a fized output as long as there is a

mixing demand. Check wiring between sensor and control unit. Verify all connections

and inspect wire insulation and sensor for damage. To clear the error message from the

control after the sensor has been repaired, press the Item button

Mix Reset Fault Messages (continued)

Sensor Resistance Chart

VIEW

OUTDR

VIEW

BOIL

VIEW

BOIL

VIEW

MIX

VIEW

MIX

Temperature Resistance

Temperature Resistance

Temperature Resistance

Temperature Resistance

°F

°C

°F

°C

°F

°C

°F

°C

-50

-46

490,813

20

-7

46,218

90

32

7,334

160

71

1,689

-45

-43

405,710

25

-4

39,913

95

35

6,532

165

74

1,538

-40

-40

336,606

30

-1

34,558

100

38

5,828

170

77

1,403

-35

-37

280,279

35

2

29,996

105

41

5,210

175

79

1,281

-30

-34

234,196

40

4

26,099

110

43

4,665

180

82

1,172

-25

-32

196,358

45

7

22,763

115

46

4,184

185

85

1,073

-20

-29

165,180

50

10

19,900

120

49

3,760

190

88

983

-15

-26

139,402

55

13

17,436

125

52

3,383

195

91

903

-10

-23

118,018

60

16

15,311

130

54

3,050

200

93

829

-5

-21

100,221

65

18

13,474

135

57

2,754

205

96

763

0

-18

85,362

70

21

11,883

140

60

2,490

210

99

703

5

-15

72,918

75

24

10,501

145

63

2,255

215

102

648

10

-12

62,465

80

27

9,299

150

66

2,045

220

104

598

15

-9

53,658

85

29

8,250

155

68

1,857

225

107

553