Mix Reset Control Display Parameters

Display

Parameter

Notes

OUTDOOR

Current outdoor air temperature as measured by the outdoor sensor. This is also the

TEMP

default display for the control. (OUTDOOR DSGN

≠ OFF)

MIX

Current mixed supply water temperature as measured by the mixing sensor

TEMP

MIX TARGET

Target mixed supply is the temperature the control is currently trying to maintain at the

TEMP

mixing sensor

BOILER

Current boiler temperature as measured by the boiler sensor. (Boiler sensor is present)

TEMP

Mix Reset Control Set-Up Parameters (continued)

Field

Display

Parameter

Definition

Range

Notes

Setting

MIX DESIGN

MIX water tempera-

70°F to 220°F

Recommended Settings

TEMP

perature required

(21°C to 93°C) High Mass Radiant (e.g., concrete):

to heat the building

120°F (49°C)

when outdoor

Low Mass Radiant (e.g., wood floor):

temperature is equal

140°F (60°C)

OUTDOOR DESIGN

Fancoil: 190°F (88°C)

TEMP

Fin Tube Convector: 180°F (82°C)
Radiator: 160°F (71°C)
Baseboard: 150°F (66°C)

BOILER

Minimum water

OFF

Recommended Settings

MINIMUM

temperature to be

80°F to 180°F

Cast iron boiler: 150°F

TEMP

returned to boiler

(27°C to 82°C) Copper tube boiler: 140°F

Condensing boiler: OFF
Electric boiler: OFF
Note: Refer to boiler installation
instructions to determine the minimum
allowable return temperature

WARM

Outdoor tempera-

35°F to 100°F

When the outdoor temperature exceeds

WEATHER

ture above which

(1°C to 37°C)

the WWSD setting, the controller will not

SHUTDOWN

the controller will

OFF

enable the boiler. It is typical to set the

TEMP

not activate the

WWSD value equal to the ROOM

boiler

DESIGN TEMP. The OFF setting defeats
the WWSD logic

ENGLISH/

Parameters to be

°F or °C

METRIC

displayed in
Farenheit or
Celsius

ESCAPE

Exit set up menu

To escape the set up menu, press either
the

or

key

ADJUST

BOIL

°

F

MIN

ADJUST

°

F

ADJUST

Display

Fault

Notes

EEPROM

The control was unable to read a piece of information from its EEPROM. This error can

FAULT

be caused by a noisy power source. The control will load the factory defaults and stop
operation until all the settings are verified

OUTDOOR

The control is no longer able to read the outdoor sensor due to a short circuit. In this

SENSOR

case, the control assumes an outdoor temperature of 32°F (0°C) and continues operation.

SHORT

Check wiring between outdoor sensor and control unit. Verify all connections and inspect

CIRCUIT

wire insulation and sensor for damage. To clear the error message from the control after
the sensor has been repaired, press the Item button

Mix Reset Fault Messages

VIEW

VIEW

OUTDR