The control was unable to read a piece of information from its EEPROM. This error can

FAULT

be caused by a noisy power source. The control will load the factory defaults and stop
operation until all the settings are verified

OUTDOOR

The control is no longer able to read the outdoor sensor due to a short circuit. In this

SENSOR

case, the control assumes an outdoor temperature of 32°F (0°C) and continues operation.

SHORT

Check wiring between outdoor sensor and control unit. Verify all connections and inspect

CIRCUIT

wire insulation and sensor for damage. To clear the error message from the control after
the sensor has been repaired, press the Item button

OUTDOOR

The control is no longer able to read the outdoor sensor due to an open circuit. In this

SENSOR OPEN

case, the control assumes an outdoor temperature of 32°F (0°C) and continues operation.

CIRCUIT

Check wiring between outdoor sensor and control unit. Verify all connections and inspect
for broken wire or damaged sensor. To clear the error message from the control after
the sensor has been repaired, press the Item button

BOILER

The control is no longer able to read the boiler sensor due to a short circuit. In this

SENSOR

case, if the BOIL MIN adjustment is set to OFF the control does not operate the Boiler

SHORT

contact. If the BOIL MIN adjustment is not set to OFF and a boiler demand is present,

CIRCUIT

the Boiler contact will operate for up to 10 minutes of a 20 minute cycle. Check wiring
between outdoor sensor and control unit. Verify all connections and inspect wire
insulation and sensor for damage. To clear the error message from the control after
the sensor has been repaired, press the Item button

BOILER

The control is no longer able to read the boiler sensor due to a short circuit. In this

SENSOR

case, if the BOIL MIN adjustment is set to OFF the control does not operate the Boiler

OPEN

contact. If the BOIL MIN adjustment is not set to OFF and a boiler demand is present,

CIRCUIT

the Boiler contact will operate for up to 10 minutes of a 20 minute cycle. Check wiring
between outdoor sensor and control unit. Verify all connections and inspect wire
insulation and sensor for damage. To clear the error message from the control after
the sensor has been repaired, press the Item button

Boiler Reset Controller Display Parameters

Display

Parameter

Notes

OUTDOOR

Current outdoor air temperature as measured by the outdoor sensor. This is also the

TEMP

default display for the control

BOILER

Current boiler supply water temperature as measured by the boiler sensor

TEMP

BOILER

Target boiler supply is the temperature the control is currently trying to maintain at the

TARGET TEMP

boiler sensor

Boiler Reset Controller Fault Messages

VIEW

VIEW

OUTDR

VIEW

OUTDR

VIEW

BOIL

VIEW

BOIL

Mix Reset Control Set-Up Parameters

Field

Display

Parameter

Definition

Range

Notes

Setting

ROOM DESIGN

The room design

35°F to 100°F

If the original heating system design

TEMP

temperature used

(1°C to 37°C)

criteria are unknown, the ROOM

in the original heat

DESIGN TEMP should be set to the

loss calculation for

estimated highest typical (non set-

the building

back) thermostat setting

OUTDOOR

The outdoor design

-60°F to +45F If the original heating system design

DESIGN TEMP

temperature used

(-51°C to 7°C) criteria are unknown, the OUTDOOR

in the original heat

DESIGN TEMP should be set to the

loss calculation for

estimated lowest expected outdoor

the building

temperature based on geographical
location