Boiler reset controller display parameters, Boiler reset controller fault messages, Mix reset control set-up parameters – Bell & Gossett 210668B Z-4M User Manual
Page 4

Display
Fault
Notes
EEPROM
The control was unable to read a piece of information from its EEPROM. This error can
FAULT
be caused by a noisy power source. The control will load the factory defaults and stop
operation until all the settings are verified
OUTDOOR
The control is no longer able to read the outdoor sensor due to a short circuit. In this
SENSOR
case, the control assumes an outdoor temperature of 32°F (0°C) and continues operation.
SHORT
Check wiring between outdoor sensor and control unit. Verify all connections and inspect
CIRCUIT
wire insulation and sensor for damage. To clear the error message from the control after
the sensor has been repaired, press the Item button
OUTDOOR
The control is no longer able to read the outdoor sensor due to an open circuit. In this
SENSOR OPEN
case, the control assumes an outdoor temperature of 32°F (0°C) and continues operation.
CIRCUIT
Check wiring between outdoor sensor and control unit. Verify all connections and inspect
for broken wire or damaged sensor. To clear the error message from the control after
the sensor has been repaired, press the Item button
BOILER
The control is no longer able to read the boiler sensor due to a short circuit. In this
SENSOR
case, if the BOIL MIN adjustment is set to OFF the control does not operate the Boiler
SHORT
contact. If the BOIL MIN adjustment is not set to OFF and a boiler demand is present,
CIRCUIT
the Boiler contact will operate for up to 10 minutes of a 20 minute cycle. Check wiring
between outdoor sensor and control unit. Verify all connections and inspect wire
insulation and sensor for damage. To clear the error message from the control after
the sensor has been repaired, press the Item button
BOILER
The control is no longer able to read the boiler sensor due to a short circuit. In this
SENSOR
case, if the BOIL MIN adjustment is set to OFF the control does not operate the Boiler
OPEN
contact. If the BOIL MIN adjustment is not set to OFF and a boiler demand is present,
CIRCUIT
the Boiler contact will operate for up to 10 minutes of a 20 minute cycle. Check wiring
between outdoor sensor and control unit. Verify all connections and inspect wire
insulation and sensor for damage. To clear the error message from the control after
the sensor has been repaired, press the Item button
Boiler Reset Controller Display Parameters
Display
Parameter
Notes
OUTDOOR
Current outdoor air temperature as measured by the outdoor sensor. This is also the
TEMP
default display for the control
BOILER
Current boiler supply water temperature as measured by the boiler sensor
TEMP
BOILER
Target boiler supply is the temperature the control is currently trying to maintain at the
TARGET TEMP
boiler sensor
Boiler Reset Controller Fault Messages
VIEW
VIEW
OUTDR
VIEW
OUTDR
VIEW
BOIL
VIEW
BOIL
Mix Reset Control Set-Up Parameters
Field
Display
Parameter
Definition
Range
Notes
Setting
ROOM DESIGN
The room design
35°F to 100°F
If the original heating system design
TEMP
temperature used
(1°C to 37°C)
criteria are unknown, the ROOM
in the original heat
DESIGN TEMP should be set to the
loss calculation for
estimated highest typical (non set-
the building
back) thermostat setting
OUTDOOR
The outdoor design
-60°F to +45F If the original heating system design
DESIGN TEMP
temperature used
(-51°C to 7°C) criteria are unknown, the OUTDOOR
in the original heat
DESIGN TEMP should be set to the
loss calculation for
estimated lowest expected outdoor
the building
temperature based on geographical
location
ADJUST
ROOM
°
F
ADJUST
DSGN
OUTDR
°
F