beautypg.com

Warning, Installation to concrete ceilings, Eb h – Peerless-AV LCC-36S - Installation User Manual

Page 5: Bh e, Illustration a

background image

5 of 12

ISSUED: 09-27-04 SHEET #: 100-9004-8 10-08-12

Installation to Concrete Ceilings

Drill two 5/16" (8 mm) dia. holes to a minimum depth
of 2.5" (64 mm). Attach ceiling plate (B) using two
concrete anchors (H) and #14 x 2.5" wood screws (E)
as shown in Illustration A and 1, 2, and 3 (below).
Tighten all fasteners.

• Tighten wood screws fi rmly, but do not overtighten.

Overtightening can damage the bolt, greatly reducing
its holding power.

• Never tighten in excess of 80 in • lb (9 N.M.).

WARNING

• Concrete anchors are not intended for attachment to

concrete wall covered with a layer of plaster, drywall,
or other fi nishing material. If mounting to concrete
wall covered with plaster/drywall is unavoidable, plas-
ter/drywall (up to 5/8" thick) must be counterbored as
shown below. If plaster/drywall is thicker than 5/8",
custom fasteners must be supplied by installer (not
evaluated by UL).

WARNING

1

E

B

H

Illustration A

CONCRETE CEILING

CUT

A

W

A

Y

VIEW

INCORRECT

CORRECT

wall

plate

wall

plate

plaster/
dry wall

plaster/
dry wall

concrete

concrete

1

3

2

H

Drill holes and insert anchors (H).

Place plate (B) over anchors (H) and secure with screws (E).

Tighten all fasteners.

B

H

E

concrete
surface