Symptom

Possible cause

Remedy

Fault code is shown as 14 and the
icon

is lighting on LCD

display and alarm is continuously
sounding.

The UPS shut down
automatically because
short circuit occurs on the
UPS output.

Check output wiring and if
connected devices are in
short circuit status.

Fault code is shown as 1, 2, 3, 4,
11, 12, 13 and 41 on LCD display
and alarm is continuously
sounding.

A UPS internal fault has
occurred. There are two
possible results:
1. The load is still supplied,

but directly from AC power
via bypass.
2. The load is no longer

supplied by power.

Contact your dealer

Battery backup time is shorter
than nominal value

Batteries are not fully
charged

Charge the batteries for at
least 5 hours and then
check capacity. If the

problem still persists,
consult your dealer.

Batteries defect

Contact your dealer to
replace the battery.