09: Programmable outlets setting

Interface

Setting

Parameter 3: Set up backup time limits for
programmable outlets.

0-999: setting the backup time limits in minutes from
0-999 for programmable outlets which connect to
non-critical devices on battery mode.

10: Backup time setting for outlets

Interface

Setting

Parameter 3: Set up backup time on battery mode for
general outlets.
0-999: setting the backup time in minutes from 0-999

for general outlets on battery mode.
0: When setting as “0”, the backup time will be only 10
seconds.

999: When setting as “999”, the backup time setting will
be disabled.

00: Exit setting

3-6. Operating Mode Description

Operating mode Description

LCD display

Online mode

When the input voltage is within
acceptable range, UPS will provide pure
and stable AC power to output. The UPS

will also charge the battery at online
mode.

ECO mode

Energy saving mode:
When the input voltage is within voltage
regulation range, UPS will bypass
voltage to output for energy saving.

Frequency

Converter mode

When input frequency is within 40 Hz to

70 Hz, the UPS can be set at a constant
output frequency, 50 Hz or 60 Hz. The
UPS will still charge battery under this

mode.

Battery mode

When the input voltage is beyond the

acceptable range or power failure and
alarm is sounding every 4 second, UPS
will backup power from battery.