Bypass mode

When input voltage is within acceptable
range but UPS is overload, UPS will enter

bypass mode or bypass mode can be set
by front panel. Alarm is sounding every
10 second.

Standby mode

UPS is powered off and no output supply
power, but still can charge batteries.

3-7. Faults Reference Code
Fault event

Fault code Icon Fault event

Fault code Icon

Bus start fail

01

x

Inverter voltage Low

13

x

Bus over

02

x

Inverter output short

14

Bus under

03

x

Battery voltage too high 27

Bus unbalance

04

x

Battery voltage too low

28

Inverter soft start fail

11

x

Over temperature

41

x

Inverter voltage high

12

x

Over load

43

3-8. Warning indicator

Warning

Icon (flashing)

Alarm

Low Battery

Sounding every second

Overload

Sounding twice every second

Battery is not connected

Sounding every second

Over Charge

Sounding every second

Site wiring fault

Sounding every second

EPO enable

Sounding every second

Over temperature

Sounding every second

Charger failure

Sounding every second

Out of bypass voltage range

Sounding every second


NOTE: “Site Wiring Fault” function can be enabled/disabled via software. Please check
software manual for the details.