10

EN

05: ECO voltage range setting

Interface

Setting

Parameter 2 & 3: Set the acceptable high voltage point
and low voltage point for ECO mode by pressing Down key

or Up key.
HLS: High loss voltage in ECO mode in parameter 2.
For 200/208/220/230/240 VAC models, the setting range

in parameter 3 is from +7V to +24V of the nominal voltage.
For 100/110/115/120/127 VAC models, the setting range
in parameter 3 is from +3V to +12V of the nominal voltage.
LLS: Low loss voltage in ECO mode in parameter 2.

For 200/208/220/230/240 VAC models, the setting range
in parameter 3 is from -7V to -24V of the nominal voltage.
For 100/110/115/120/127 VAC models, the setting voltage

in parameter 3 is from -3V to -12V of the nominal voltage.

06: Bypass enable/disable when UPS is off

Interface

Setting

Parameter 3: Enable or disable Bypass function. You may
choose the following two options:
ENA: Bypass enable

DIS: Bypass disable

07: Bypass voltage range setting

Interface

Setting

Parameter 2 & 3: Set the acceptable high voltage point

and acceptable low voltage point for Bypass mode by
pressing the Down key or Up key.
HLS: Bypass high voltage point

For 200/208/220/230/240 VAC models:
230-264: setting the high voltage point in parameter 3
from 230Vac to 264Vac.
For 100/110/115/120/127 VAC models:

120-132: setting the high voltage point in parameter 3
from 120Vac to 132Vac
LLS: Bypass low voltage point

For 200/208/220/230/240 VAC models:
170-220: setting the low voltage point in parameter 3
from 170Vac to 220Vac

For 100/110/115/120/127 VAC models:
85-115: setting the low voltage point in parameter 3 from
85Vac to 115Vac.

08: Programmable outlets enable/disable

Interface

Setting

Parameter 3: Enable or disable programmable outlets.

ENA: Programmable outlets enable
DIS: Programmable outlets disable