PowerWalker VFI 1000R LCD User Manual

Page 16

background image

13

EN

4. Troubleshooting

If the UPS system does not operate correctly, please solve the problem by using the table

below.

Symptom

Possible cause

Remedy

No indication and alarm even
though the mains is normal.

The AC input power is not
connected well.

Check if input power cord
firmly connected to the
mains.

The AC input is connected

to the UPS output.

Plug AC input power cord

to AC input correctly.

The icon

and the warning

code

flashing on LCD

display and alarm is sounding
every second.

EPO function is activated. Set the circuit in closed

position to disable EPO

function.

The icon

and

flashing on

LCD display and alarm is sounding
every second.

Line and neutral

conductors of UPS input
are reversed.

Rotate mains power socket

by 180° and then connect
to UPS system.

The icon

and

flashing

on LCD display and alarm is

sounding every second.

The external or internal
battery is incorrectly

connected.

Check if all batteries are
connected well.

Fault code is shown as 27 and the

icon

is lighting on LCD

display and alarm is continuously
sounding.

Battery voltage is too high
or the charger is fault.

Contact your dealer.

Fault code is shown as 28 and the

icon

is lighting on LCD

display and alarm is continuously
sounding.

Battery voltage is too low

or the charger is fault.

Contact your dealer.

The icon

and

is

flashing on LCD display and alarm
is sounding twice every second.

UPS is overload

Remove excess loads from

UPS output.

UPS is overloaded. Devices
connected to the UPS are
fed directly by the
electrical network via the

Bypass.

Remove excess loads from
UPS output.

After repetitive overloads,
the UPS is locked in the
Bypass mode. Connected

devices are fed directly by
the mains.

Remove excess loads from
UPS output first. Then shut
down the UPS and restart

it.

Fault code is shown as 43 and The

icon

is lighting on LCD

display and alarm is continuously
sounding.

The UPS shut down
automatically because of

overload at the UPS
output.

Remove excess loads from
UPS output and restart it.