4 contact the service center – PowerWalker VFI 6000LE Plus User Manual

Page 32

background image

29

2) The UPS should be charged once every 4 to 6 months if it has not

been used for a long time.

3) In the regions of hot climates, the battery should be charged/

discharged every 2 months. The charging time should be >12 hours.

4) In normal conditions, the battery life lasts 3 to 5 years. If the battery

is found in bad condition, earlier replacement should be made.

5) Do not replace the battery individually. All batteries should be

replaced at the same time following the instructions of the supplier.

4.4 Contact the service center

If contact the service center for trouble shooting, please provide the

information as following:

Model name of product.

Serial number of product.

The date when the problem found.

LED display status.

Buzzer alarm status.

Mains power condition

Load type and capacity.

Environment temperature, ventilation status.

The information (battery capacity, quantity) of the external battery

pack if the UPS is long back up model.

Other information for complete description of the problem.