Make sure a DC breaker or other protection device between UPS and

external battery pack is installed. If not, please install it carefully. Switch

off the battery breaker before installation.

Pay highly attention to the rating battery voltage marked on the rear

panel, the connection with wrong battery voltage may cause

permanent damage of the UPS. Make sure the voltage of the

battery pack is correct.

Pay highly attention to the polarity marking on external battery

terminal block, and make sure the correct battery polarity is

connected. Wrong connection may cause permanent damage of the

UPS.

Make sure the battery input wiring is correct before power on. The

wire current spec, color, position, connection and conductance

reliability should be checked carefully. Make sure the +/- polarity is

correct, not reverse, no short circuit.

Make sure the protective earth ground wiring is correct. The wire

current spec, color, position, connection and conductance reliability

should be checked carefully.

Make sure the mains input & output wiring is correct. The wire

current spec, color, position, connection and conductance reliability

should be checked carefully. Make sure the L/N site is correct, not

reverse, no short circuit.

Install the terminal block cover on the rear panel of the UPS.

2.4 Installation for communication software (optional)

1) Connect the communication cable between UPS and PC. If the

port is RS232, please lock the secure screw both on UPS and PC

after connection. If the port is USB, it has Plug and Play function.

2) Please refer to the guide manual of software or contact the

service center for installation and operation of management

(monitoring) software.