beautypg.com

4 electrical specification – PowerWalker VFI 6000LE Plus User Manual

Page 12

background image

9

1.5.4 Electrical Specification

Model

6K

6KS

10K

10KS

Power

6000VA / 4200W

10000VA / 7000W

Input

Current (Max.)

30A

32A

47A

50A

Voltage Range

176~276VAC @ full load (110~276VAC @ half load)

Frequency Range

46 ~ 54Hz @ 50Hz system / 56 ~ 64Hz @ 60Hz system

Input Power Factor

0.98 @ full load

Output

Voltage

208*/220/230/240VAC (sine-wave)

Synchronizing mains input @ line mode

Frequency

50/60Hz ±0.05Hz @ battery mode

THD

4% ( Linear load )

Voltage Regulation

2%

Line mode: 60s @ 100%~130%; 1s @ > 130%

Overload Capacity

Battery mode: 10s @ 100%~130%; 1s @ >130%

Efficiency @ full linear load

Line Mode

89%

Battery Mode

84%

89%

88%

89%

Battery & Charger @ 25

Total battery rating voltage

144VDC

240VDC

192VDC

240VDC

Backup Time (Half Load)

>8min

>9min

Recharge Time (to 90%)

8Hours

8Hours

Charging Current (Max.)

1A

4A

1A

4A

Discharging Current (Max.)

24

39

Rated Charging Voltage

163.8

273

218.4

273

*: If the rating output voltage is 208VAC, the rating power will be decreased to 90%.