Symptom

Possible cause

Remedy

Fault code is shown as 14 and

the icon

is lighting on

LCD

display

and

alarm

is

continuously sounding.

The

UPS

shut

down

automatically

because

short circuit occurs on the
UPS output.

Check output wiring and if
connected devices are in
short circuit status.

Fault code is shown as 1, 2, 3, 4,
11, 12, 13 and 41 on LCD display
and

alarm

is

continuously

sounding.

A UPS internal fault has
occurred. There are two
possible results:
1.

The

load

is

still

supplied, but directly from
AC power via bypass.
2. The load is no longer
supplied by power.

Contact your dealer

Battery backup time is shorter
than nominal value

Batteries are not fully
charged

Charge the batteries for at
least 5 hours and then
check capacity. If the
problem

still

persists,

consult your dealer.

Batteries defect

Contact your dealer to
replace the battery.

The icon

and the warning

code

flashing on LCD

display and alarm is sounding
every second.

Fan is locked or not
working

Check fans and notify
dealer!!



5. Storage and Maintenance

Operation

The UPS system contains no user-serviceable parts. If the battery service life (3~5 years
at 25°C ambient temperature) has been exceeded, the batteries must be replaced. In this
case, please contact your dealer.

Storage

Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a cool, dry

location. During storage, recharge the battery in accordance with the following table:

Storage Temperature

Recharge Frequency

Charging Duration

-25°C - 40°C

Every 3 months

1-2 hours

40°C - 45°C

Every 2 months

1-2 hours

Be sure to deliver the spent battery to a recycling facility or ship it to your
dealer in the replacement battery packing material.