3.3. Audible Alarm

Battery Mode

Sounding every 4 seconds

Low Battery

Sounding every second

Overload

Sounding twice every second

Fault

Continuously sounding

Bypass Mode

Sounding every 10 seconds

3.4. LCD display wordings index

Abbreviation

Display content

Meaning

ENA

Enable

DIS

Disable

ESC

Escape

HLS

High loss

LLS

Low loss

BAT

Battery

CF

Converter

EP

EPO

FA

Fan

TP

Temperature

CH

Charger



3.5. UPS Setting

There are three parameters to set up the
UPS.

Parameter 1: It’s for program alternatives.
There are 10

programs to set up. Refer to

below table.
Parameter 2 and parameter 3 are the
setting options or values for each
program.

Parameter 1

Parameter 2

Parameter 3