PowerWalker VFI 1000RM LCD User Manual

Page 15

background image

14

EN

parameter 3 is from -3V to -12V of the nominal voltage.

06: Bypass enable/disable when UPS is off

Interface

Setting

Parameter 3: Enable or disable Bypass function. You may choose
the following two options:
ENA: Bypass enable
DIS: Bypass disable

07: Bypass voltage range setting

Interface

Setting

Parameter 2 & 3: Set the acceptable high voltage point and
acceptable low voltage point for Bypass mode by pressing the
Down key or Up key.
HLS: Bypass high voltage point
For 200/208/220/230/240 VAC models:
230-264: setting the high voltage point in parameter 3 from 230Vac
to 264Vac.
For 100/110/115/120/127 VAC models:
120-132: setting the high voltage point in parameter 3 from 120Vac
to 132Vac
LLS: Bypass low voltage point
For 200/208/220/230/240 VAC models:
170-220: setting the low voltage point in parameter 3 from 170Vac
to 220Vac
For 100/110/115/120/127 VAC models:
85-115: setting the low voltage point in parameter 3 from 85Vac to
115Vac.

08: Programmable outlets enable/disable

Interface

Setting

Parameter 3: Enable or disable programmable outlets.
ENA: Programmable outlets enable
DIS: Programmable outlets disable

09: Programmable outlets setting

Interface

Setting

Parameter 3: Set up backup time limits for programmable outlets.
0-999: setting the backup time limits in minutes from 0-999 for
programmable outlets which connect to non-critical devices on
battery mode.

10: Backup time setting for outlets

Interface

Setting

Parameter 3: Set up backup time on battery mode for general
outlets.
0-999: setting the backup time in minutes from 0-999 for general
outlets on battery mode.
0:

When setting as “0”, the backup time will be only 10 seconds.

999:

When setting as “999”, the backup time setting will be

disabled.

00: Exit setting