beautypg.com

PowerWalker VFI 1000RM LCD User Manual

Page 11

background image

10

EN

3. Operations

3.1. Button operation

Button

Function

ON/Mute Button

 Turn on the UPS: Press and hold ON/Mute button for at least 2

seconds to turn on the UPS.

 Mute the alarm: When the UPS is on battery mode, press and hold

this button for at least 5 seconds to disable or enable the alarm
system. But it’s not applied to the situations when warnings or errors
occur.

 Up key: Press this button to display previous selection in UPS setting

mode.

 Switch to UPS self-test mode: Press and hold ON/Mute buttons for 5

seconds to enter UPS self-testing while in AC mode, ECO mode, or
converter mode.

OFF/Enter Button

 Turn off the UPS: Press and hold this button at least 2 seconds to

turn off the UPS in battery mode. UPS will be in standby mode under
power normal or transfer to Bypass mode if the Bypass enable
setting by pressing this button.

 Confirm selection key: Press this button to confirm selection in UPS

setting mode.

Select Button

 Switch LCD message: Press this button to change the LCD message

for input voltage, input frequency, battery voltage, output voltage and
output frequency. It will return back to default display when pausing
for 10 seconds.

 Setting mode: Press and hold this button for 5 seconds to enter UPS

setting mode when UPS is in standby mode or bypass mode.

 Down key: Press this button to display next selection in UPS setting

mode.

ON/Mute + Select
Button

 Switch to bypass mode: When the main power is normal, press

ON/Mute and Select buttons simultaneously for 5 seconds. Then
UPS will enter to bypass mode. This action will be ineffective when
the input voltage is out of acceptable range.


3.2. LCD Panel