ISOCON-3 USERS GUIDE

4.1.3 Millivolt (mV) Input

Select the range from the table below and set Switch S1 to the required values.

mV Range

1

2

3

4

5

6

7

8

9

10 11 12

0-25mV

0

0

0

0

0

0

0

1

1

1

0

0

0-50mV

0

0

0

1

0-100mV

0

0

1

0

0-125mV

0

1

0

0

0-150mV

1

0

0

0

0-200mV

0

0

1

1

0-250mV

0

1

0

1

0-300mV

1

0

0

1

0-500mV

0

1

1

0

0-600mV

1

0

1

0

0-1000mV

0

1

1

1

0-1200mV

1

0

1

1

-125 to +125mV

1

1

0

0

-125 to +1000mV

1

1

1

1

0

0

0

1

1

1

0

0

Switch S1

And then select the required setting from the table below for switch S2

mV Range

1

2

3

4

5

6

7

8

9

10 11 12

0

1

0

0

0

0

1

1

0

0

0

0

0

1

0

0

1

0

1

0

0

0

0

0

All Unipolar

Ranges (e.g.

0-500mV)

Switch S2

Bipolar Ranges

(e.g.

-125 to +125mV)

!

! WARNING !

DO NOT OPEN UNIT OR ADJUST SWITCHES WITH

POWER SUPPLY, INPUT OR OUTPUT CONNECTED




Please note that PC Software is available to provide information on

switch settings for your input and output requirements.


Page

8

IIG-060901