Note: The Vlinx Serial Server Manager

software contains default parameter values

that are common to most Modbus networks.

1. Change the Description of the serial port if

needed.

2. Set the Mode to RS-232, RS-422 (4 wire),

RS-485 (2 wire) or RS-485 (4 wire).

3. Set the Baud Rate to control the speed of the port.

Valid rates range between 75 and 230.4k bits per

second.

4. Stop Bits controls the number of bits for end of

character.

5. Parity controls the error checking mode, with

options of No Parity, Odd, Even, Mark and Space.

Q

uick

S

tart

G

uide

Isolated Industrial

Ethernet to Serial Servers

VESR321

Document number – pn9758_VESR321-xx_r0_4212_qsg

Recommended Accessories

and Power Supplies

5

Set Up Serial Port

There are additional configuration pages that may be

accessed by selecting “Next” at the bottom of each

page, or by selecting the desired page from the

vertical list in the left-hand column.

The Vlinx Serial Server Manager defaults to options

like “Network” and “I don’t know the IP of the

device.” If the defaults meet your needs you don’t

need to set or change them.

If you have completed the configuration, click Save to

save the configuration to the serial server. Allow 15

seconds for the Serial Server to reboot.

Click “Connect.” You should see a list of all

devices on the network, including your new

device. If you do not see your new device,

please refer to the Troubleshooting tips.

You may now log out.