beautypg.com

Service instructions (cont’d.), Page 25 – Peerless Water 5600_5600 Econominder User Manual

Page 25

background image

Printed in U.S.A.

Page 25

MODEL 5600 & 5600 ECONOMINDER

®

Service Instructions (Cont’d.)

10. Push resin tank back to the plumbing connections

and engage meter ports with by-pass valve or yoke.

11. Attach two clips and screws at by-pass valve or

yoke. Be sure clip legs are firmly engaged with lugs.

12. Return by-pass or inlet valving to normal service

position. Water pressure should now be applied to
the conditioner, and any by-pass line shut off.

13. Check for leaks at all seal areas.
14. Plug electrical cord into outlet.
15. Set time of day. Make sure the control valve is in the

service position.

16. Rotate program wheel counter-clockwise until it

stops at regeneration position.

17. Start regeneration cycle manually if water is hard.
18. Plug cable into meter cover. Rotate cable to align

drive flat if necessary.

F.

TO REPLACE METER COVER AND/OR IMPELLER

1.

Unplug electrical cord from outlet.

2.

Turn off water supply to conditioner:

a. If the conditioner installation has a “three valve”

by-pass system, first open the valve in the by-
pass line, then close the valves at the
conditioner inlet and outlet.

b. If the conditioner has an integral by-pass valve,

put it in the by-pass position.

c. If there is only a shut-off valve near the

conditioner inlet, close it.

3.

Relieve water pressure in the conditioner by putting
the control in the backwash position momentarily.
Return the control to the service position.

4.

Pull cable out of meter cover.

5.

Remove four screws on cover

6.

Lift cover off of meter module, discard O-ring.

7.

Remove and inspect impeller for gear or spindle
damage, replace if necessary.

8.

Apply silicone lubricant to new O-ring and assemble
to the smallest diameter on meter cover.

9.

Assemble cover to meter module. Be sure impeller
spindle enters freely into cover. Press firmly on
cover and rotate if necessary to assist in assembly.

10. Replace four screws and tighten.
11. Return by-pass or inlet valving to normal service

position. Water pressure should now be applied to
the conditioner, and any by-pass line shut off.

12. Check for leaks at all seal areas.
13. Plug electrical cord into outlet.
14. Set time of day. Make sure the control valve is in the

service position.

15. Rotate program wheel counter-clockwise until it

stops at regeneration position.

16. Start regeneration cycle manually if water is hard.
17. Plug cable into meter cover. Rotate cable to align

drive flat if necessary.