Series 2000 batch fan / heater – Grain Systems PNEG-1135 User Manual
Page 58

2001 Top Dry Service School
58
Diagnostic Mode
Turn the Control Power off .
Hold down the Program Tempera-
ture switch.
Turn the Control Power switch on
with the Program Temperature switch
held down.
Press the Increase switch until 8 is on
the display.
Press the Program Temperature switch
again.
Press the Program Dry time switch to
engage the Fan starter-Fan will be
displayed.
Press the Increase switch to make the
ignitor spark-IN will be displayed.
Press the Program Temperature switch
to open the LP and Main Solenoid- LP
will be displayed.
Press the Start switch to open the
Cycle solenoid -CS will be displayed.
Turn the control power off to exit
the Diagnostic mode.
CAUTION: DO NOT ATTEMPT BELOW PROCEDURE WITH GAS LINE CONNECTED.
Series 2000 Batch Fan / Heater
Software Diagnostics
- PNEG-1890 (16 pages)
- PNEG-595 (26 pages)
- PNEG-1472 (30 pages)
- PNEG-897 (58 pages)
- PNEG-838 (4 pages)
- PNEG-1755 (36 pages)
- PNEG-524 (24 pages)
- PNEG-1080 (2 pages)
- PNEG-728 (47 pages)
- PNEG-673 (57 pages)
- PNEG-1717 (88 pages)
- PNEG-823 (42 pages)
- PNEG-630-6S (23 pages)
- PNEG-1876 (80 pages)
- PNEG-102 (2 pages)
- PNEG-366 (51 pages)
- PNEG-1626 (1 page)
- PNEG-1874 (78 pages)
- PNEG-1798 (34 pages)
- PNEG-1927 (4 pages)
- PNEG-924 (2 pages)
- PNEG-582 (26 pages)
- PNEG-012 (46 pages)
- PNEG-1797 (86 pages)
- PNEG-546 (26 pages)
- PNEG-951 (102 pages)
- PNEG-1650 (92 pages)
- PNEG-1649 (50 pages)
- PNEG-1376 (88 pages)
- PNEG-361 (46 pages)
- PNEG-338 (32 pages)
- PNEG-1276 (78 pages)
- PNEG-1283 (22 pages)
- PNEG-1089 (14 pages)
- QSG-001 (2 pages)
- PNEG-950 (96 pages)
- PNEG-1590 (3 pages)
- PNEG-501 (33 pages)
- PNEG-1447 (68 pages)
- PNEG-707GSI (446 pages)
- PNEG-349 (32 pages)
- PNEG-236 (22 pages)
- PNEG-743 (16 pages)
- PNEG-900 (54 pages)
- PNEG-1935 (92 pages)