2003 top dry service school – Grain Systems PNEG-1314 User Manual
Page 28

2003 Top Dry Service School
2 8
Fan 1 Motor Overload
The thermal overload in the control box on fan
number one has tripped, indicating an overcurrent
condition. The overload must be reset manually.
Fan 2 Motor Overload
The thermal overload in the control box on fan
number two has tripped, indicating an overcurrent
condition. The overload must be reset manually.
Fan 1 Loss Of Airflow
The contacts on the airswitch, located in the bin
sidewall and attached to fan and heater number one,
have opened due to the fan not turning, or the airswitch
may need to be adjusted.
Drying Chamber Overflow
The grain level in the drying chamber has
reached the drying chamber overflow rotary switch.
Grain will have to be dumped from the drying chamber
to the storage chamber before the unit can be restarted.
This error indicates that either the drying chamber high
level rotary switch is faulty or the time on the Load
delay or Aux. 1 delay needs to be lowered.
Bin Grain High Limit Full
The grain level in the storage chamber has
reached the storage chamber high level rotary switch
located 3 feet below the fan and heater(s). Grain will
have to be removed from the storage chamber before
the unit can be restarted.
Bin High Limit Switch Bad
The storage chamber high level switch has
failed. Both the normally open and the normally closed
sides of the switch are in the same state.
Out Of Grain
The out of grain timer has ran for longer than it
was set. Either you are out of grain or the fill system is
filling to slow.