PNEG-900 Series 2000 Autoflow Fan/Heater and Control Installation Instructions
33
Natural Gas (NG)
This dryer is designed to operate on natural gas. Natural gas units have a larger orifice to accommodate
lower pressures sometimes found with natural gas and do not have vaporizer coils like liquid propane
units. A regulated pressure of 10 PSI minimum, 30 PSI maximum must be provided at the field connection
point on the fan/heater unit, with gas available in sufficient volume to maintain the operating pressure.
See the
“Fuel Systems and Recommendations Chart” for natural gas (NG) to determine the correct
size line to run to the dryer. Have a qualified gas service person inspect the installation to be sure
everything is installed according to local codes and ordinances.
After installation is complete, check all connections for leaks with liquid detergent or comparable. Wear
rubber gloves and eye protection.
Figure 3W NG Line Field Connection
Fuel System Specifications and Recommendations Natural Gas (NG)
Dryer
Fan Size
Dryer
Horsepower
Maximum Heat
Capacity BTU
per Hour
Maximum Fuel
Flow Cubic Ft.
per Hour
Minimum
Line Size
Orifice Size
Minimum
Operating
Pressure
Maximum
Operating
Pressure
36"
15
5 Million
5280
2"
1/2"
1 lb.
7 lbs.
40"
15
5.5 Million
5965
2"
17/32"
1 lb.
7 lbs.
42"
30
9 Million
9536
2"
43/64"
1 lb.
7 lbs.
42"
40
9.5 Million
10445
2"
45/64"
1 lb.
7 lbs.
WARNING
Do not use flame for leak testing.