beautypg.com

Maintenance, Led diagnostics, Terminal identification – Altronix AL600ULB Installation Instructions User Manual

Page 2

background image

Altronix is not responsible for any typographical errors.

140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
web site: www.altronix.com, e-mail: [email protected], Lifetime Warranty, Made in U.S.A.
IIAL600ULB Rev. 100302

H14M

MEMBER

Note: When used in fire alarm, burglar alarm or access control
applications, “AC Fail” relay must be used to provide a visual
indication of AC power on.

Maintenance:

Unit should be tested at least once a year for the proper
operation as follows:
Output Voltage Test: Under normal load conditions
the DC output voltage should be checked for proper
voltage level (refer to Power Supply Voltage Output
Specification chart).
Battery Test: Under normal load conditions check that the
battery is fully charged, check specified voltage both at the
battery terminal and at the board terminals marked
[+ BAT –] to ensure that there is no break in the battery connection wires.
Note: Maximum charging current under discharge is 0.7 amp.
Note: Expected battery life is 5 years; however, it is recommended changing batteries in 4 years or less if needed.

LED Diagnostics:

Red (DC) Green (AC) Power Supply Status
ON

ON

Normal operating condition.

ON

OFF

Loss of AC, Stand-by battery supplying power.

OFF

ON

No DC output

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

Terminal Identification:

Terminal Legend Function/Description
AC/AC

Connect 28VAC to these terminals from 2 connected in parallel transformers.

+ DC –

12VDC or 24VDC @ 6 amp continuous non-power limited output.

AC FAIL
NC, C, NO

Used to notify loss of AC power, e.g. connect to annunciator/alarm panel. Relay normally

energized when AC power is present. Contact rating 1 amp @ 30VDC. AC Fail condition will

report approximately one (1) minute after the loss of AC. To delay report for 6 hours cut jumper J1

on the Power Supply Board (AC trouble output delay option). If this mode is selected, the Power

Supply Board must be reset by removing all power to it for 30 seconds.

BAT FAIL
NC, C, NO

Used to indicate low battery condition, e.g. connect to alarm panel. Relay normally energized

when DC power is present. Contact rating 1 amp @ 30VDC. Low battery conditions will report

approximately 21VDC (24VDC output setting) or approximately 10.5VDC (12VDC output setting).

Battery presence detection will report approximately 1 minute after battery remains undetected

+ BAT –

Stand-by battery connections. Maximum charge current 0.7 amp.

+

DC ---

DC

AC

AC

+

BAT ---

OPEN = 24V SW1 CLOSED = 12V

RL2

RL3

AC

RLY1

PTC2

AC TROUBL

E

DELA

Y

OPTION

IC3

IC2

AC
FA

IL

NC C NO

BA

T

FA

IL

NC C NO

Fig. 1