AL168 Series

Overview:

These AL168CB Series Multi-Output Power Supplies provide 16VAC/18VAC distributed via eight (8) PTC protected
outputs for powering multiple security system or access control panels.

Eight (8) Output AL168 Reference Chart:

Altronix

Model Number

Output

Voltage

Total

Output

Current

(Power)

Number

of

Outputs

PTC

Protected

Outputs

Fuse

Protected

Outputs

Output

Current

(max

per

output)

Main Fuse

Ratings

on Board

115VAC

50/60Hz

Input

Current

AL168CB

16VAC

6 amp

8

x

-

2.5 amp 10 amp/250V

0.9 amp

18VAC 5.5 amp

AL168175CB

16VAC

10 amp

8

x

-

2.5 amp 15 amp/250V

1.45 amp

AL168300CB

16VAC

18 amp

8

x

-

2.5 amp

15 amp/32V

2.7 amp

18VAC

16 amp

AL168300CBM

16VAC

18 amp

8

x

-

2.5 amp

15 amp/32V

2.7 amp

18VAC

16 amp

AL168600CB

16VAC

40 amp

8

x

-

6 amp

Two (2)

15 amp/32V

5.4 amp

18VAC

36 amp

• Surge suppression.
• AC power LED indicator.
• Illuminated power disconnect circuit breaker with
manual reset (except AL168CB).
• Unit maintains camera synchronization.
• Ease of installation saves time & eliminates costly labor.
• Spare fuses included.

Enclosure Dimensions

(H x W x D)

:

AL168CB:
8.5” x 7.5” x 3.5” (215.9mm x 190.5mm x 88.9mm)
AL168175CB and AL168300CBM:
8.5” x 7.5” x 3.75” (215.9mm x 190.5mm x 95.25mm)
AL168300CB and AL168600CB:
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm)

Specifications:

Installation Instructions:

1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the
enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s
upper keyholes over the two upper screws, level and secure. Mark the position of the lower two holes. Remove the
enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes over the two
upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 7).
Secure enclosure to earth ground.
2. Turn OFF main switch (except AL168CB) (Figs. 2-5, pgs. 4-6).
3. All units are factory set for 16VAC operation.
For 18VAC operation, adjust unit prior to mounting and applying power as follows: Change the wire position so that
the black wire [18V] is connected to the terminal marked [P] and the yellow wire [16V] is connected to the
terminal marked [S].
4. Connect AC power to the black and white flying leads of the transformer(s)
(Figs. 1-5, pgs. 4-6). Use 18 AWG or larger for all power connections.
5. Measure output voltage before connecting devices. This helps avoiding potential damage.
Terminals marked [1P - 8P] are positive of the same polarity.

CAUTION: Determine the maximum operating voltage of the equipment being powered before adjusting

the output voltage.
6. Connect devices to terminals marked [1P - 1N through 4P - 4N] on PD4/PD4CB board (Figs. 3 & 5, pgs. 5-6)
or terminals marked [1P - 1N through 8P - 8N] on PD8/PD8CB board (Figs. 1, 2 & 4, pgs. 4-5), carefully
observing polarity.
7. Turn main switch to the “RESET” (ON) position (except AL168CB) (Figs. 3-5, pgs. 5-6).