LED Diagnostics:

Red (DC)

Green (AC)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Battery backup is powering output.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or missing stand-by battery. No DC output.

Terminal Identification:

Terminal Legend Function/Description
AC

Low voltage AC input.

TRG1 & TRG2

These input terminals are designed to connect to the normally closed
outputs of an access control or fire alarm relay. These terminals control [LOCK+],
and [STRIKE+], as well as AL175ULB output relay contacts [N.C., N.O., C]

LOCK +

This terminal provides DC output voltage when [TRG1] and [TRG2] are shorted
together and are typically used to power Mag Locks.

STRIKE+

This terminal provides DC output voltage when [TRG1] and [TRG2] are unshorted
and are typically used to power Electric Strikes.

N.C., N.O., C

Isolated dry Form “C” contacts. Shorting [TRG1] and [TRG2] together causes
these contacts to switch. They are typically used for controlling multiple
AL175ULBs with fire alarm tie-in (Fig. 4 and Fig. 5, pg. 4).

AUX+

Continuous positive (+) DC power output voltage. It is not affected by TRG1, TRG2 operation.

COM --

Common negative (-) output (ground).

FACP

Spare wiring terminal used for fire alarm tie-in application (Fig. 3, pg. 4).

+ BAT --

Stand-by battery connections.

AC Fail
N.C., C, N.O.

Used to notify loss of AC e.g connect audible device or alarm panel relay normally energized
when AC power is present. Contact rating 1 amp @ 28VDC.