Line ground neutral, Unswitched 120vac power mains (non-power limited), Fig. 2 – Altronix AL802ULADA Installation Instructions User Manual
Page 7: Green lead, Optional hookup diagram, Fig. 2b fig. 2a, Line ground neutral green lead

AL802ULADA
- 7 -
These circuits are used to
monitor AC and Bat Fail and
will cause a simultaneous trouble
condition to the FACP's IN1 and IN2
Digital Communicator or
Local Annunciator Dry output Contact
(Form "C" contacts)
4-wire Smoke
Detector
+
--
+
--
4-wire Smoke
Detector
Fire
Alarm
Control
Panel
(FACP)
EOL Power
Supervision Relay
(Not Supplied)
EOL
Resistor
from
FACP
SW1
-- DC +
SW2
+ OUT1 --
OUT1 OUT2 OUT3 OUT4
INP1 INP2
FAULT
NC
CN
OC
"F
AUL
T" NC
OUT1
OUT3
OUT2
OUT4
INPUT SELECT
TEMPORAL
STROBE SYNC
IN > OUT SYNC
IN1+ IN1--
IN2--
IN2+
C "DRY1" NC
RET1+ RET1--
RET2--
RET2+
C "DRY2" NC
+ OUT2 --
+ OUT3 --
+ OUT4 --
INPUT SELECT
TEMPORAL
STROBE SYNC
IN > OUT SYNC
-- AUX +
UPPER TERMINALS
LOWER TERMINALS
Addressable
Control Module
Trigger Output
See Note 2
line
ground
neutral
Green Lead
Use separate knockout.
Keep 1/4" spacing from
non power limited wiring
Power-Limited Outputs
2.5 amp per
output in alarm
(total= 8 amp)
(Supervised)
Supervised Non-Supervised
Non-Supervised
Non-Supervised
RESET
unswitched 120VAC
power mains
(non-power limited)
NC C NO
NC C NO NC C NO
AC Local
AC DELA
Y
BAT FAIL
AC FAIL
AC LED
VR1
Fig. 2
These circuits are used to
monitor AC and Bat Fail and
will cause a simultaneous trouble
condition to the FACP's IN1 and IN2
Digital Communicator or
Local Annunciator Dry output Contact
(Form "C" contacts)
4-wire Smoke
Detector
+
--
+
--
4-wire Smoke
Detector
Fire
Alarm
Control
Panel
(FACP)
EOL Power
Supervision Relay
(Not Supplied)
EOL
Resistor
from
FACP
SW1
-- DC +
SW2
+ OUT1 --
OUT1 OUT2 OUT3 OUT4
INP1 INP2
FAULT
NC
CN
OC
"F
AUL
T" NC
OUT1
OUT3
OUT2
OUT4
INPUT SELECT
TEMPORAL
STROBE SYNC
IN > OUT SYNC
IN1+ IN1--
IN2--
IN2+
C "DRY1" NC
RET1+ RET1--
RET2--
RET2+
C "DRY2" NC
+ OUT2 --
+ OUT3 --
+ OUT4 --
INPUT SELECT
TEMPORAL
STROBE SYNC
IN > OUT SYNC
-- AUX +
UPPER TERMINALS
LOWER TERMINALS
Addressable
Control Module
Trigger Output
See Note 2
line
ground
neutral
Green Lead
Use separate knockout.
Keep 1/4" spacing from
non power limited wiring
Power-Limited Outputs
2.5 amp per
output in alarm
(total= 8 amp)
(Supervised)
Supervised Non-Supervised
Non-Supervised
Non-Supervised
RESET
unswitched 120VAC
power mains
(non-power limited)
NC C NO
NC C NO NC C NO
AC Local
AC DELA
Y
BAT FAIL
AC FAIL
AC LED
VR1
NC
CN
OC
"F
AUL
T" NC
Fig. 2b
Fig. 2a
These circuits are used to
monitor AC and Bat Fail and
will cause a simultaneous trouble
condition to the FACP's IN1 and IN2
Digital Communicator or
Local Annunciator Dry output Contact
(Form "C" contacts)
4-wire Smoke
Detector
+
--
+
--
4-wire Smoke
Detector
Fire
Alarm
Control
Panel
(FACP)
EOL Power
Supervision Relay
(Not Supplied)
EOL
Resistor
from
FACP
SW1
-- DC +
SW2
+ OUT1 --
OUT1 OUT2 OUT3 OUT4
INP1 INP2
FAULT
NC
CN
OC
"F
AUL
T" NC
OUT1
OUT3
OUT2
OUT4
INPUT SELECT
TEMPORAL
STROBE SYNC
IN > OUT SYNC
IN1+ IN1--
IN2--
IN2+
C "DRY1" NC
RET1+ RET1--
RET2--
RET2+
C "DRY2" NC
+ OUT2 --
+ OUT3 --
+ OUT4 --
INPUT SELECT
TEMPORAL
STROBE SYNC
IN > OUT SYNC
-- AUX +
UPPER TERMINALS
LOWER TERMINALS
Addressable
Control Module
Trigger Output
See Note 2
line
ground
neutral
Green Lead
Use separate knockout.
Keep 1/4" spacing from
non power limited wiring
Power-Limited Outputs
2.5 amp per
output in alarm
(total= 8 amp)
(Supervised)
Supervised Non-Supervised
Non-Supervised
Non-Supervised
RESET
unswitched 120VAC
power mains
(non-power limited)
NC C NO
NC C NO NC C NO
AC Local
AC DELA
Y
BAT FAIL
AC FAIL
AC LED
VR1
Fig. 2c
Trouble Memory
Reset Button
Common trouble
Input/Output
Optional Hookup Diagram: